14
A Time-Current Curve Approach to Arc-Flash Hazard Analysis Jeanne M. Avendt Distribution System Engineer UNITED SERVICES GROUP 17845 East Highway 10 Elk River, MN 55330 763.241.5793 July 9, 2008

A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

  • Upload
    lamcong

  • View
    216

  • Download
    1

Embed Size (px)

Citation preview

Page 1: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

A Time-Current Curve Approach to Arc-Flash Hazard Analysis

Jeanne M. Avendt Distribution System Engineer UNITED SERVICES GROUP

17845 East Highway 10 Elk River, MN 55330

763.241.5793

July 9, 2008

Page 2: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

2 of 14

DEFINITIONS

Some of the following definitions were obtained from the IEEE Guide for Performing Arc-Flash Hazard Calculations – Standard 1584 - 20021 Arc-flash hazard: A dangerous condition associated with the release of energy caused by an electric arc. Arcing fault current: The fault current flowing through an electrical arc plasma, also called fault current and arc current. Available fault current: The electrical current at a given location that can be provided by the available source considering the impedance, or resistance, of the current path. Bolted fault current: A short circuit or electrical contact between two conductors at different potentials in which the impedance or resistance between the conductors is essentially zero. Circuit: A conductor or system of conductor through which an electric current is intended to flow. Electrical hazard: A dangerous condition in which inadvertent or unintentional contact or equipment failure can result in shock, arc-flash burn, thermal burn, or blast. Electrical shock: Physical stimulation that occurs when electrical current passes through the body. Energized: Electrically connected to or having a source of voltage. Exposed (live parts): Capable of being inadvertently touched or approached nearer than a safe distance by a person. It is applied to parts that are not suitably guarded, isolated, or insulated. Fault current: A current that flows from one conductor to ground or to another conductor due to an abnormal connection (including an arc) between the two. Flash hazard analysis: A method to determine the risk of personal injury as a result of exposure to incident energy from an electrical arc-flash. Flash protection boundary2: An approach limit at a distance from live parts that are uninsulated or exposed within which a person could receive a second degree burn. Also called an arc-flash protection boundary.

1 Institute of Electrical and Electronics Engineers, Inc., IEEE Guide for Performing Arc-Flash Hazard Calculations – IEEE Std. 1584™ – 2002, (New York: Institute of Electrical and Electronics Engineers, Inc., 2002). 2 NFPA 70E-2000 additionally defines a “limited approach boundary”, a “prohibited approach boundary”, and a “restricted approach boundary”.

Page 3: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

3 of 14

Incident energy: The amount of energy impressed on a surface at a certain distance from the source generated during an electrical arc event. Incident energy is measured in joules per centimeter squared (J/cm2) or calories per centimeter squared (cal/cm2).1 Working distance: The distance between the possible arc point and the head and body (torso) of the worker positioned in a place to perform the assigned task.

1 To convert from cal/cm2 to J/cm2, multiply cal/cm2 by 4.184 (See IEEE 1584 – 2002 Annex E for further information.

Page 4: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

4 of 14

ABSTRACT: The 2007 Edition of the National Electric Safety Code, Section 41.410.A.3 – page 246, has regulated that employers conduct an arc-flash hazard assessment prior to January 1, 2009 to ensure adequate protection of employees from exposure to electrical arcs when working near energized equipment. This paper details a method of arc-flash hazard analysis using the IEEE Standard 1584-2002, IEEE Guide for Performing Arc-Flash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash hazard of a device or work location at various fault currents. INTRODUCTION: Arc-flash hazard analysis is important in determining the personal protective equipment (PPE) required to keep personnel safe when working with energized equipment. Contact with energized equipment is a commonly known risk; however, exposure to incident energy from an electrical arc is sometimes overlooked. Whether the electrical arc is a result of equipment failure, equipment operation or switching, or unintentional contact, the resultant incident energy can result in serious and life-threatening third-degree burns and/or exposure to molten metal and other projectiles. With adequate PPE and knowledge of the hazard category at a particular work location, the likelihood of a serious injury is reduced. As stated in 2007 Edition of the National Electric Safety Code, Section 41.410.A.3 – page 246:

“Effective as of January 1, 2009, the employer shall ensure that an assessment is performed to determine potential exposure to an electric arc for employees who work on or near energized parts or equipment. If the assessment determines a potential employee exposure greater than 2 cal/cm2 exists…, the employer shall require employees to wear clothing or a clothing system that has an effective arc rating not less than the anticipated level of arc energy.”1

There is much discussion regarding how thorough an arc-flash hazard assessment must be. A complete examination of the system would require assessment at each and every possible work location, a task that is unrealistic to complete. Even if this task was undertaken, some of the accepted analysis methods pose some concerns as to whether the assessment considers the ‘most likely’ fault scenarios. This paper will first discuss the fundamentals of arc-flash hazard analysis using the IEEE Std. 1584-2002 methodology of arc-flash analysis. It will then go on to discuss the results of the arc-flash analysis provided by IEEE Std. 1584-2002. Finally, it will discuss a TCC-based methodology that provides further arc-flash hazard risk assessment for varying scenarios. The TCC-based methodology provides the information to deduce appropriate PPE at any work location given basic knowledge of available fault currents for the given system. 1 Institute of Electrical and Electronics Engineers, Inc., Nation Electric Safety Code® C2-2007, (New York: Institute of Electrical and Electronics Engineers, Inc., 2006), pg 246.

Page 5: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

5 of 14

ARC-FLASH FUNDAMENTALS: This section will cover the fundamentals of arc-flash hazard analysis. The methodology used in this section is that of IEEE Std. 1584-2002, IEEE Guide for Performing Arc-Flash Hazard Calculations. Please reference the IEEE Standard 1584-2002, IEEE Guide for Performing Arc-Flash Hazard Calculations for detailed equations and calculation parameters. First and foremost, when considering arc-flash hazard there are four (4) primary factors that determine the hazard category:

1. System voltage. 2. Bolted fault current – calculated at the location/equipment to be assessed and

subsequently used to calculate the theoretical arcing fault current. 3. Working distance – as measured from the personnel’s head/torso to the location

of the arc source. 4. Fault clearing time.

The IEEE Std. 1584-2002, IEEE Guide for Performing Arc-Flash Hazard Calculations provides a spreadsheet to ease the assessment of the arc-flash hazard. While detailed equations for the various calculations are provided in Std. 1584, the spreadsheet ensures higher confidence that, provided the correct values are entered, the results are accurate. It must be said that, aside from the four factors listed above, there are other factors determining the arc-flash hazard. For example, the gap between the conductors at the location in which the arc occurs is a factor in the both the arcing current calculation and the resultant incident energy calculation. The spreadsheet provides a typical gap based on the equipment type and system voltage. More specific conductor gap values could be substituted, if desired; however, the conductor gap could vary based on location of the arc-flash event. Due to the unpredictable nature of fault events, a typical / average value is suitable for calculations. In the instance of a fault due to equipment failure or operation, the conductor gap is somewhat predictable because of the design of the physical equipment. In the case of inadvertent contact being the source of the fault, the gap in which the arc occurs can vary greatly. Of the four primary factors that determine the arc-flash hazard category, two (2) have a larger impact than the others: working distance and fault clearing time. The working distance is defined as the distance from the personnel’s head/torso to the location of the arc source and does not consider hands, arms, or legs. While incident energy exposure to one’s hands is something to be avoided, injury to appendages is not considered life-threatening. Incident energy quickly decays as distance from the fault source increases; therefore, the hazard is reduced with distance. An arc-flash boundary distance should be provided in any arc-flash hazard analysis. An arc-flash boundary is the distance from the arc source in which the incident energy is less than 1.2 cal/cm2, the energy needed to obtain a second degree burn. In the author’s opinion, fault clearing time plays the largest role in the arc-flash hazard category. The longer one is exposed to fault incident energy, the greater the degree of injury. Due to this, low fault currents are often more dangerous than high fault currents.

Page 6: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

6 of 14

A time-current curve (TCC) is frequently used to show the relationship between current (amps) and response time (seconds). Most protective devices have an inverse characteristic: as current increase, time decreases. Figure 1 illustrates the TCC for an 80T fuse element. Note that the TCC is displayed using a non-linear logarithmic (log) scale.

Figure 1 80T Fuse Time-Current Curve

Clearing times can be extrapolated from the TCC by first selecting a current at which the response time is desired. For this example, we will use 1000 A. The vertical line at the 1000 A mark is followed up until it intersects the device response curve. Fuse elements typically have a minimum melt and total clear time associated with the device response. The minimum melt time is the time characteristic in which the fuse element first begins to melt due to the fault energy. The total clear time is the time in which the manufacturer anticipates the fuse element will completely melt thus removing the fault. In the case of arc-flash analysis, the author uses the total clear time as it is the slower of

Page 7: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

7 of 14

the two characteristics. As previously stated, the longer the clearing time, the greater the arc-flash hazard. At the point where the 1000 A vertical line intersects the 80T total clear curve, a line is drawn horizontally to the time axis. The point at which the horizontal line intersects the time axis is the time in which a 1000 A fault will be cleared, in this case, approximately 0.7 seconds. It is important to note that the ‘current’ axis (x-axis) can be displayed in amps or multiple of the device pickup. Additionally, the ‘time’ axis (y-axis) can be displayed in seconds or cycles. Some TCC's contain a line between the first and second multiples of 10, such as the one in Figure 1. For example, a line indicating 1500 A exists between the 1000 A and 2000 A lines. In evaluating the arc-flash hazard category, the first step is to calculate the bolted fault current at the evaluation point. This can be done by hand or with the aid of modeling software. In the case of substation transformers, it is usually relevant to look at the available source data. Contrary, when evaluating distribution transformers, an infinite bus calculation can be used since, for most systems, a value very close to the infinite bus fault is readily obtainable given the source. Once bolted fault currents are calculated, the arcing fault current can be calculated either by hand or with the aid of the IEEE 1584 spreadsheet. The arcing fault current value will be lower than the bolted fault current value due to the impedance of the arc, and will vary according to the system voltage. Refer to the IEEE Standard 1584-2002, IEEE Guide for Performing Arc-Flash Hazard Calculations, section 5.2 for arcing current equations. For some voltage classes, a reduced arcing fault current will be calculated in addition to the arcing fault current. In calculating the arcing fault current, equipment class, system voltage and grounding type must be considered. In using the IEEE 1584 spreadsheet, the equipment class and system voltage are considered when determining the conductor gap, which is a variable in the calculation of the arcing fault current. Once the arcing fault current has been determined, and the reduced arcing fault current if required, the protective device trip time can be input. As previously stated, the fault clearing time has the largest impact on what the hazard category will be. The protective device that will clear a fault at the analysis location must be determined. In the example of a distribution transformer, this is the transformer’s highside (primary) fuse. Using the protective device’s time-current curve, the protective device’s clear time must be input into the incident energy formula or IEEE 1584 spreadsheet. It is the author’s recommendation to use the total clear time as a worse case (slowest) scenario when a fuse is the upstream protective device. The trip time lookup should be done for the reduced arcing fault current, if required. In addition to the trip time, an opening time is required. For various equipment classes the opening time may vary therefore the manufacturer's literature should be referenced. In the case of a fuse element in which the total clear time (as opposed to the minimum melt time) is used, an opening time of a cycle will suffice. Refer to the IEEE Standard 1584-2002, IEEE Guide for Performing Arc-Flash Hazard Calculations, Table 1 for IEEE opening time recommendations.

Page 8: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

8 of 14

Working distance is another important factor in assessing the arc-flash hazard. As previously stated, incident energy quickly decays as distance from the arc source increases. Typical working distances include work done with one’s hands: 12 – 15 inches (304.8 – 381 mm), and work done with a hotstick or shotgun stick: 7 – 8 feet (2133.6 – 2438.4 mm). It is recommended that arc-flash analysis be performed for all possible working distances. Table 1, below, illustrates the effect that each variable has on the arc-flash hazard category, provided that all other variables remain the same.

Table 1 Arc-flash Hazard Variable Relationships

Provided all other parameters remain the same:

As x increases: Hazard category: x = Conductor gap Increases x = Working distance Decreases x = System voltage Increases

x = Bolted fault current Neither – results in an increase in arcing fault current

x = Arcing fault current Neither – typically results in an increase in clearing time

x = Clearing time Increases Equipment class changes effect: Arc-flash boundary Grounding changes effect: Arc-flash boundary

ARC-FLASH ASSESSMENT RESULTS: Following the input of required parameters, the IEEE 1584 spreadsheet calculates various values that are helpful in assessing the arc-flash hazard. Foremost is the assigned hazard category for the working distance that was input into the spreadsheet. (Note: the IEEE 1584 specifies the hazard ONLY at the input working distance. If the actual working distance is less than the input value, the actual hazard category will be greater than calculated). Hazard categories are defined by exposure to incident energy in cal/cm2, which is available as a reference parameter within the spreadsheet. Table 2, below, illustrates the various categories and incident energy ranges corresponding to each category.

Page 9: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

9 of 14

Table 2 Hazard Category as a Function of Incident Energy

Arc-flash Hazard Category

Minimum cal/cm2 Maximum cal/cm2 Risk Category 0 1.2 0

1.2001 4 1 4.001 8 2 8.001 25 3

25.001 40 4 40.001 No maximum X

In addition to a hazard category assessment, the IEEE 1584 spreadsheet calculates a flash protection boundary, or the distance in which less than 1.2 cal/cm2 is impressed on the head/torso of personnel in the event of an arc-flash. If outside of the flash protection boundary, personnel should not receive injuries greater than a second degree burn. The flash protection boundary is independent of the working distance that was input into the spreadsheet. While the IEEE 1584 spreadsheet provides assessment that satisfies the requirements of the NESC, it is the author’s opinion that the arc-flash hazard can vary greatly at any given work location due to the multitude of variables that exist. Possible fault values at a single work location are only truly limited by the maximum available fault current at that location. The magnitude of the fault can be influenced greatly by a number of factors, including but no limited to, the nature/cause of the fault, the arcing resistance and even the atmospheric humidity. As previously stated, it is the lower magnitude faults that pose a greater risk, due to increased clearing time; however, in the author’s experience, the majority of faults are within 70% of the maximum available fault current at a given location. It is a tough decision to make, but while worst case scenario events should be examined, it is the events of higher probability that should be planned for. In addition to the challenges presented by the range of potential fault magnitudes, is the issue that results from the millions of possible work locations. It would be time consuming and labor intensive to assess the arc-flash hazard at all possible work locations. The author’s preferred method is to perform assessments at some fixed points, but then use a TCC based approach to deal with the unassessed areas. It is advised that arc-flash hazard assessment be performed for the following locations at multiple working distances:

• Faults within the substation cleared by the transformer highside, lowside and/or other applicable protective device.

• Faults cleared by the feeder protective device upon leaving the substation. • Faults downstream or within padmounted switchgear or other underground or

overhead switching points that are routinely operated. • Lowside distribution transformer faults cleared by the distribution transformer

highside protective device.

Page 10: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

10 of 14

Figure 2 provides a simplified one-line diagram that highlights the points that are typically assessed using the IEEE 1584 spreadsheet.

Figure 2 Simplified One-Line w/ Arc Flash

Analysis Points

Other points on the system, such as tap fuses, can be addressed using the TCC based approach to arc-flash assessment which is later discussed. Table 3 demonstrates typical results obtained using the IEEE 1584 spreadsheet. Some cells have been removed from the table to simplify results. In the case of the distribution transformers, voltage and current parameters are with respect to the transformer lowside; however, the arc clearing time is determined using the characteristics of the highside fuse, which would clear the lowside fault. Also note the units in which parameters are expressed.

Page 11: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

11 of 14

Table 3 IEEE 1584 Spreadsheet Example

for Figure 2 One-Line

TIME-CURRENT CURVE ARC-FLASH HAZARD ASSESSMENT: A time-current curve based approach to arc-flash assessment entails superimposing the hazard category at various current magnitudes upon the TCC for a specific protective device. The result is a color-coded TCC in which the hazard category can be extrapolated for any available fault current. All other variables affecting the arc-flash hazard category must remain the same, such as working distance, arc gap, system voltage, etc. This approach allows quick assessment for any work location given knowledge of the protective device upstream of the work location. It is the protective device upstream of the work location that will clear any fault in the immediate vicinity of personnel performing work. Figure 3 and 4 provide examples of an arc-flash hazard TCC. Note the specified working distance and system voltage. While not documented, all other variables also remained the same.

Page 12: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

12 of 14

Figure 3 80T Fuse Arc-Flash Hazard TCC at 15”

Page 13: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

13 of 14

Figure 4 80T Fuse Arc-Flash Hazard TCC at 8’

Page 14: A Time-Current Curve Approach to Arc-Flash Hazard · PDF fileFlash Hazard Calculations, to create a time-current curve (TCC) reflecting the arc-flash ... the response time is desired

14 of 14

INTERPRETING AN ARC-FLASH TCC: One can extrapolate the arc-flash hazard category from an arc-flash TCC by simply referencing the color coded hazard at the desired current. In an example of line work being performed on a fused tap, the personnel must only know the protective device upstream of the work location and approximate fault currents to determine the approximate arc-flash hazard and appropriate PPE. In the case of the 80T fuse shown in Figure 3 and 4, and assuming fault currents greater than 1000 A, it can be seen that the arc-flash hazard at 15” is a category 1 and a category 0 at 8’. Discussion often arises regarding what can be considered a reasonable minimum fault value when using an arc-flash TCC. While low magnitude faults can occur, in most cases, the fault current quickly escalates as arcing further reduces the fault impedance. The worst case scenario is always a low magnitude fault near the device pickup, but this is not the most likely scenario. Fault magnitudes can vary greatly, but a good place to start when considering the most likely fault scenario would be approximately 6 – 10 times the device pickup. This range is determined using field experience and assumptions regarding the power system protection. CONCLUSION: While the hazard created by arc-flash events is nothing new, NESC regulations have prompted those with personnel exposed to electrical systems to further investigate and plan for the associated hazard. The vast number of unpredictable variables makes arc-flash hazard assessment some what of an imperfect science. With reasonable assumptions and basic system knowledge, the use of arc-flash TCC's provides a method of determining the hazard category at virtually any location without performing time consuming calculations at seemingly infinite work locations. As an added benefit, it is in the author’s experience that the reaction of personnel tends to be more favorable and understanding when the arc-hazard potential is presented in a visual medium, as opposed to a data-packed spreadsheet. In a short safety meeting the basics of reading an arc-flash TCC can be explained. Personnel often reflect on fault magnitudes that they have commonly seen and the associated hazard in the case of an arc-flash event. Even when not required by company policy, linemen have opted to wear a face-shield when performing a certain task only because they were not aware of the potential arc-flash hazard should something go wrong.