4
105 0 C Tri-rated SWITCHGEAR & Control Panel Wires

20100427761Tri-RatedPanelWire Draka Cables

Embed Size (px)

DESCRIPTION

Great

Citation preview

Page 1: 20100427761Tri-RatedPanelWire Draka Cables

1050CTri-rated

SWITCHGEAR& Control Panel Wires

Page 2: 20100427761Tri-RatedPanelWire Draka Cables

105˚C Tri-rated Switchgear &Control Panel Wires

ApplicationFlexible Tri-rated hook up wires Type PW01 have beenspecifically designed for use in the switch, control, relay andinstrumentation panels of power circuits and for purposessuch as internal connectors in rectifier equipment, motorstarters and controllers.

By combining three national standards in one product, PW01is suitable for equipment installations required to meet bothEuropean and North American wiring regulations and codesof practice. This facilitates design, simplifies purchasing and cuts inventory costs.

Technical DataTemperature range: Recognised by UL and CSA as heat-resisting with a maximum conductor operating temperatureof 105˚C.

NOTE: BS 6231 specifies a maximum conductor operating temperature of 90˚C for continuous use.Under certain conditions these cables can be operated at up to 105˚C, ‘annex a’ of BS 6231 gives full details.

PW01 has good low temperature flexibility, meeting cold bend tests down to -30˚C.

Maximum working voltage: UL, CSA 600V r.m.s.

BS 6231 (Uo/U) 600/1000V r.m.s

Oil resistance: PW01 is recognised by UL and CSA asresistant to oil at temperatures up to 60˚C.

Spread of flame: VW-1, FT-1, BS 4066 : Part 1, EN 50265and IEC 60332-1.

Applicable standards:

1. Underwriters Laboratory Listed. Conforms toSubject 758 Appliance Wiring Material for Styles1015, 1028, 1283 and 1284 as applicable. UL FileNo E54385.

2. Canadian Standards Association approved.Complies with Standard C22.2, No.127, Type TEW. CSA File No. LL43273.

3. British Standards. Manufactured to BS 6231Type CK.

Construction1 Flexible plain annealed copper wire conductor

to BS 6360 (Class 5).

2 Plasticised PVC insulation specially formulated tocombine excellent electrical performance with robustmechanical properties, yet still complying with UL, CSAand BS tests for spread of flame on a single vertical cable.

1

2

2

Page 3: 20100427761Tri-RatedPanelWire Draka Cables

Ref. No.

Nominal Class Approx Nominal Nominal Approx UL StyleCross- of AWG Conductor Diameter Nett No.

Sectional Conductor Diameter of Cable WeightArea

mm 2 mm mm kg/km

PW01-0.50 0.5 5 22 0.93 2.7 12 1015

PW01-075 0.75 5 20 1.14 2.9 15 1015

PW01-1.0 1.0 5 18 1.32 3.1 18 1015

PW01-1.5 1.5 5 16 1.6 3.4 23 1015

PW01-2.5 2.5 5 14 2.0 3.8 34 1015

PW01-4.0 4.0 5 12 2.6 4.4 50 1015

PW01-6.0 6.0 5 10 3.3 5.1 71 1015

PW01-10.0 10.0 5 8 4.2 6.8 123 1028

PW01-16.0 16.0 5 6 5.7 9.2* 209 1283

PW01-25.0 25.0 5 4 7.1 10.6 296 1283

PW01-35.0 35.0 5 2 8.5 12.0 400 1283

PW01-50.0 50.0 5 1 10.3 14.7* 582 1284

PW01-70.0 70.0 5 2/0 12.4 16.8* 796 1284

PW01-95.0 95.0 5 3/0 14.5 18.9 1025 1284

PW01-120.0 120.0 5 4/0 16.0 20.4 1282 1284

*Marginally exceeds diameter of BS 6231.

PHYSICAL DATA

Conductor Maximum Maximum Approx. VoltsCross-Sectional Conductor Current Drop per Amp

Area Resistance Rating per Metre

mm 2 Ω/km ( 20ºC) A mV

0.5 37.10 11 46.0

0.75 24.70 14 31.0

1.0 18.50 17 22.0

1.5 12.70 21 15.0

2.5 7.60 30 9.1

4.0 4.71 41 5.7

6.0 3.14 53 3.8

10.0 1.82 75 2.2

16.0 1.16 100 1.4

25.0 0.743 136 0.89

35.0 0.527 167 0.64

50.0 0.36 204 0.45

70.0 0.259 259 0.32

95.0 0.196 321 0.24

120.0 0.153 374 0.19

ELECTRICAL DATA

The current ratings tabulated left are based onsingle cables in free air, amaximum conductortemperature of 105˚C andan ambient temperature of 45˚C.The volts drop tabulatedabove are for single cablesonly. For circuits of singlephase 50Hz a.c. or twowire d.c. the figures shownshould be multiplied by 2and for three phase 50Hza.c. multiplied by 1.732.NOTE: The temperaturerise in a conductor dueto current flow should belimited to 40˚C.

Sizes and colours notindicated left can bemanufactured tospecial order.Sizes over 120mm2 are bi-rated to UL & BS 6231. The CSA standard does notcover sizes above 120mm2. Alternatives to the standardcable can also be suppliede.g., tinned copperconductors, solid conductors(Class 1) or semi-rigidconductors (Class 2).

RATING FACTORS

Ambient Temp. (°C) 45 50 55 60 65 70 75

Factor (close production) 1.0 0.97 0.90 0.82 0.73 0.63 0.52

Factor (fuses to BS 3036) 1.0 0.98 0.95 0.92 0.89 0.83 0.68

RATING FACTORS FOR GROUPED CABLESWhere a number of cables are grouped together and touching, the current rating must be derated according to thenumber of loaded cables as follows:

Number of Loaded Cables 2 3 4 5 6 8 10

Factor 0.80 0.70 0.65 0.60 0.56 0.50 0.46

AVAILABILITY PW01 is included in our standard stock range, pre-packed in 100 metre lengths, in the following sizes and colours.

0.5mm2 - 2.5mm2 Black, Red, Blue, Brown, Yellow, Grey, White, Green/Yellow, Orange, Pink, Violet

4.0mm2 - 16.0mm2 Black, Red, Blue, Brown, Yellow, Grey, White, Green/Yellow

25.0mm2 - 50.0mm2 Black, Red, Blue, Yellow, Green/Yellow

70.0mm2 Black, Red, Green/Yellow

95.0mm2 Black, Red

120.0mm2 Black

3

Page 4: 20100427761Tri-RatedPanelWire Draka Cables

Prin

ted

in E

ngla

nd 1

230a

11-

99 3

k

Draka UK Ltd Industrial Cables

Alfreton RoadDerby

DE21 4AEUnited Kingdom

+44 (0)1332 345431+44 (0)1332 331237

email: [email protected]

Draka Delta Cables Jebel Ali Free Zone

P.O. Box 17159Jebel Ali

DubaiUnited Arab Emirates

009714 8836 749009714 8836 238

Draka Cables(Hong Kong) Ltd

6th FloorMTL Warehouse

Phase II, Berth OneKwai Chung Container Terminal

New TerritoriesHong Kong

00852 2410 922900852 2410 9789

Draka UK Ltd Cardinal Cables

Crowther RoadWashington

Tyne & WearNE38 OAQ

United Kingdom+44 (0)191 415 5000+44 (0)191 417 8671

email: [email protected]

All the information provided - including charts and diagrams - is believed to becorrect at the time of going to press. However, Draka UK makes no warranties asto its accuracy, and accepts no liability regarding its use. Draka UK‘s Conditions ofSale for each product specify the company’s obligations and are available onrequest. In the interests of continuous product improvement, Draka UK reservesthe right to alter specifications or materials as appropriate. The suitability ofindividual products for specific applications should be determined by the user.Draka UK accepts no liability for any incidental, indirect or consequential damagesarising from the sale, resale, use or misuse of the product.

BS EN ISO 9001 Cert. No. CS1 - 018 DerbyBS EN ISO 9002 Cert. No. CS2 - 041 LeedsBS EN ISO 9001 Cert. No. CS1 - 094 Washington

1050CTri-rated

SWITCHGEAR& Control Panel WiresBELGIUM

BRAZIL

CHINA

CZECH REPUBLIC

DENMARK

FRANCE

GERMANY

HONG KONG

MALAYSIA

NETHERLANDS

OMAN

PORTUGAL

SINGAPORE

SPAIN

THAILAND

UNITED ARAB EMIRATES

UNITED KINGDOM

U.S.A

Draka Holding N.V.have manufacturing operations

& representative officesin the following countries: