1000 PLUS SERIES

SMARTSCAN INFORMATION

SS-1K+ AUG05

ISSUE 1 Smartscan Ltd, Pywell Road, CORBY, NN17 5XJ, UK, Tel: +44 (0) 1536 401313, Fax: +44 (0) 1536 268954, Email: [email protected], www.smartscan.com

1000 PLUS SERIES LIGHT CURTAINS

HANDBOOK

Page 2: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Page 3: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

CONTENTS Page

INTRODUCTION 3 INTERFACE 5 SPECIFICATION 6 1000 PLUS SERIES LIGHT CURTAINS 7 LIGHT CURTAINS 30mm DETECTION CAPABILITY 8 LIGHT CURTAINS 40mm DETECTION CAPABILITY 9 LIGHT CURTAINS FOR PERIMETER GUARDING 10 MULTIFUNCTION SAFETY UNITS 11 ACCESSORIES 37 SAFETY SYSTEM SOLUTIONS 49 INSTALLATION SHEET 51 APPENDIX 1 65 APPENDIX 2 71

www.smartscan.com

1000 PLUS SERIES LIGHT CURTAINS

Page 4: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Page 5: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

1000 Plus Safety Light Curtains In the past safety light curtains have been very expensive, negating their use for many machine safeguarding applications. Smartscan 1000 Plus safety light curtains are offered at exceptionally low cost and as such it is now more cost effective to use light curtains rather than conventional protective screens or fences, thus opening many new areas of application for light curtains throughout industry. The 1000 Plus system incorporates many unique design features that have enabled Smartscan to severely reduce manufacturing costs. The result, a high quality range of safety light curtains at low cost. As endorsement to its reliability each 1000 Series Plus system comes complete with a full two years warranty. Connecting the 1000 Plus light curtain to a machine control system couldn’t be easier. A 24V DC supply is required to the transmitter and receiver units. Connect the two electronic output switches to the machine stop circuit and the installation is complete. There is NO interconnection cable between the transmitter and receiver units and NO control unit to install. The 1000 Plus has 22 standard models in the range. Detection heights vary from 180mm up to 1240mm in 150mm increments. 1000 Plus light curtains detect objects of 30mm and 40mm and therefore suitable for ‘hand’ detection. Two, three and four beam models, for safeguarding around the perimeter of a machine are also available. The 1000 Plus has passed Type Examination from European Notified Body, AMTRI VERITAS to the Machinery Directive. Certification provides users with an assurance that the 1000 system meets all relevant legislative safety requirements.

INTRODUCTION 3

Page 6: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Step forward safely to greater productivity

A technically advanced light curtain, offering outstanding cost effectiveness, opening the gates to new opportunities in machine guarding Typical machine safeguarding applications include: q Robots q Packaging machines q Special purpose equipment q Process machinery q Injection moulding machines q Transfer lines q Automated warehouses q Textile machinery q Electronic component assembly lines q Bottling and filling machines 1000 Plus light curtains comply with European and International Safety Standards BS EN 61496-1 and BS IEC 61496-2 Type 2. They are normally used where the risk assessment for the safety related parts of a control system, as indicated in BS EN 954-1, determines a requirement up to and including Category 3 control equipment. q EC Type Examined q Safety integrity classification EN 954-1 – Category 3 q Simple installation and alignment q Up to 10m scanning range (model dependant) q Two year manufacturers warranty Features q Slim-line enclosures q No range setting q Continually self monitoring system q Diagnostic indicators q Dual channel, fail-safe electronic outputs (control reliable) q Interface cables included q Two part system Flexible mounting options

INTRODUCTION 4

Page 7: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

(Output Signal Switching Devices) OSSD1 and OSSD2 (F6) Two independent electronic switches provide the fail-safe outputs for connection to the machine control system. Outputs ‘ON’ = 24V DC, Outputs ‘OFF’ = 0V DC. Maximum switching current for each output = 0.5A@24V. Cable colours for output switches Black = OSSD1, White = OSSD2. Power Supply A regulated power supply is required: +24V DC, up to 1.5A dependent on OSSD loads ±20%. Cable colours for power supply connections at both transmitter and receiver: Brown = +24V DC, Blue = 0V DC. Indicators F1 - Yellow ‘flashing’ indicators on the (TX) transmitter column indicates the unit is powered-up and the electronic system is operational. (There is a yellow indicator associated with every block of 6 beams in the light curtain). F2 - Yellow ‘flashing’ indicators on the (RX) receiver column indicates that communication is established between transmitter and receiver, and the light curtain is correctly aligned. Yellow ‘steady’ indicators on the (RX) receiver column indicates that the light curtain is incorrectly aligned or the light curtain detection zone is ‘blocked’. F3 - Green LED indicator on the (RX) receiver unit illuminates when the electronic output switches, OSSD1 and OSSD2 are ‘ON’ (only when the light curtain detection zone is ‘clear’ of any obstruction). F4 - Red LED indicator on the (RX) receiver unit illuminates when the electronic output switches, OSSD1 and OSSD2 are ‘OFF’ e.g. when the light curtain detection zone is ‘blocked’. If the Red LED indicator is flashing the system is in lockout. To recover from a lockout condition disconnect the transmitter and receiver from the power source and then re-apply.

INTERFACE 5

Page 8: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

1000 Plus Light Curtains

Number of beams 2 – 48 Object detection 30mm, 40mm plus 2, 3 & 4 beam perimeter systems Detection zone 180mm to 1240mm Range 0.5 – 10m (model dependent) Light type Infra-Red 880nm Response time 40ms Operating temperature

0°C to +50°C

Light curtain enclosure

IP65 (HxWxD) Hx28x41mm

Status indicators TX - Yellow (flashing) TX ‘OK’ RX - Red (steady) OSSDs ‘OFF’

- Red (flashing) system lockout RX - Green OSSDs ‘ON’ RX - Yellow (flashing) TX to RX communications established RX – Yellow (steady) incorrectly aligned or detection zone is ‘blocked’

Power supply requirement

24V DC 1.5A ± 20% reg

Current consumption 200mA transmitter + 200mA receiver (OSSD LOAD ADDITIONAL)

Light curtain connection

5m cables connected to both TX & RX units

Finish Polyester powder coated (yellow) Classification BS EN 61496-1 Type 2

BS IEC 61496-2 Type 2 BS EN 954-1 Category 3

Warranty Two Years

OUTPUTS Safety Outputs OSSD1 & OSSD2

2 x electronic switches, each rated at 24V DC, 500mA - ON = 24V DC, OFF = 0V standing current (min 20mA)

SPECIFICATION 6

Certificate Number: AV EC 1926

Certificate Number: CC/TCF/00012

Report Number: 288/4093670

amtri veritas Type Examined

FM27828

Page 9: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

The 1000 Plus light curtain represents a major step forward in light curtain design. The system continually self- tests itself and de-energises its output if a fault is detected This eliminates the need for a ’test’ input. By utilising two safety outputs 1000 Plus Series light curtains have a far higher safety integrity than those with a single output. Furthermore, the outputs are monitored by the light curtain (short circuit proof) and therefore are termed ‘control reliable’ and meet the safety requirements of BS EN 954-1 Category 3. Mechanical features The light curtain enclosure is of aluminium construction finished in a yellow polyester powder coating. An adapter bracket set is provided enabling the light curtain to be mounted from the column ends using a transmitter and receiver mounting kit (011-130). The enclosures are totally sealed making them suitable for use in wet environments. Each enclosure has integral M6 threaded slots down the sides and back so that it may be mounted from any face with no special fixtures.

1000 PLUS SERIES LIGHT CURTAINS 7

Page 10: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Each enclosure has integral M6 threaded slots down the sides and back so that it may be mounted from any face with no special fixtures. Light Curtains 30mm Detection Capability Range 0.5m to 5m

Model number

Number of beams

Detection zone (K) mm

Overall length (M) mm

Weight (TX + RX) Kg

012 - 098 6 180 190 0.3

012 – 100 12 330 340 0.5

012 – 102 18 480 490 0.7

012 – 104 24 630 640 0.8

012 – 106 30 780 790 0.9

012 – 108 36 930 940 1.1

012 – 110 42 1080 1090 1.3

012 – 112 48 1230 1240 1.5

Includes 5m transmitter cable & 5m receiver cable.

LIGHT CURTAINS 8

Note: 1000 Plus guards over 1300mm long will not be available from stock. Please contact us direct on requests for guards above this length.

Page 11: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Light Curtains 40mm Detection Capability Range 4m to 10m

Model number

Number of beams

Detection zone (K) mm

Overall length (M) mm

Weight (TX + RX) Kg

012 – 099 6 190 190 0.3

012 – 101 12 340 340 0.5

012 – 103 18 490 490 0.7

012 – 105 24 640 640 0.8

012 – 107 30 790 790 0.9

012 – 109 36 940 940 1.1

012 – 111 42 1090 1090 1.3

012 – 113 48 1240 1240 1.5

Includes 5m transmitter cable & 5m receiver cable.

LIGHT CURTAINS 9

Note: 1000 Plus guards over 1300mm long will not be available from stock. Please contact us direct on requests for guards above this length.

Page 12: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Light Curtains Perimeter Guarding Range 0.5m to 5m

Model number

Beam pitch

Overall length (M) mm

Weight (TX + RX) Kg

012 - 125 2 @ 550mm 640 0.7

012 - 126 3 @ 450mm 990 0.9

012 - 127 4 @ 400mm 1290 1.2

Includes 5m transmitter cable & 5m receiver cable.

Light Curtains Perimeter Guarding Range 4m to 10m

Includes 5m transmitter cable & 5m receiver cable.

Model number

Beam pitch

Overall length (M) mm

Weight (TX + RX) Kg

012 - 122 2 @ 550mm 640 0.7

012 - 123 3 @ 450mm 990 0.9

012 - 124 4 @ 400mm 1290 1.2

LIGHT CURTAINS 10

Page 13: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Smartscan 1000 Plus Series light curtains incorporate two fail-safe, electronic output switches. If there is a requirement for relay output switching a Multifunction Safety Unit (MFU) may be used. The MFU Type 011-149 is effectively a safety relay module, and, just like any other proprietary safety relay it provides relay output switching contacts and a choice of control functions, for example auto/manual reset and external device monitoring. An, MFU Type 011-150 has much more to offer. Not only does it provide inputs for the emergency stop function but it also has two further sets of inputs for connecting up to two light curtains. The monitored output switching contacts are rated at 250V AC, 2A with two additional electronic outputs for status indication etc. Other features include selectable auto/manual reset modes, external device monitoring (EDM) and LED indicators for all input and output channels. The unit is automatically self testing and with simultaneous monitoring between related channels it ensures the unit is suitable for Category 4 control systems as defined in BS EN 954-1.

MULTIFUNCTION SAFETY UNITS 11

Page 14: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

MFU Type 011-151 further enhances the Smartscan range of multifunction safety units. The unit incorporates a light curtain muting facility, designed specifically for those systems that require the light curtain detection zone to be inhibited, or muted, during specific periods of a machine’s operating cycle. Muting allows access through the light curtain for the passage of material or for a person to load and unload parts through the light curtain during safe periods without interrupting the machines operating cycle. MFU Type 011-151 provides a dual channel safety monitored input for automatically muting the light curtain during safe periods of machine operation. Mute signals are often derived from the machine control system or from external sensors or switches. It also provides dual inputs for a Series 1000 light curtain and a two channel emergency stop system. The monitored safety output relay switches are rated at 250V AC, 2A, for connection to a power-switching device or directly to a machines final control element. Two electronic outputs are provided one for guard status indication and the other to indicate a ‘mute on’ condition. Both are for direct connection to a PLC or indicator lamps etc. Other features include external device monitoring (EDM) and LED indicators on all inputs and outputs. Monitoring between associated input channels ensures the unit is suitable for Category 3 control systems as defined in BS EN 954-1. MFU Type 011-153 is an output switching expansion module. The unit provides 8 N/O and 2 N/C switching contacts each rated at 250V AC 4A. The expansion module operates in conjunction with MFU’s 011-149, 011-150, 011-151 and 011-154 to provide additional output switching contacts that may be required for a particular application. MFU Type 011-154 has been designed specifically for entry/exit applications where the light curtain is positioned across a conveyor. The control module provides two safety monitored inputs for signals that automatically mute the associated light curtain during safe periods of the machine operation. Mute signals are usually derived

MULTIFUNCTION SAFETY UNITS 12

Page 15: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

from external PE sensors, limit switches or, the machine control system. For additional integrity a 3rd mute input channel (mute enable) is provided. This input is often connected to a ‘conveyor run’ signal to enable a mute condition, ONLY when the associated conveyor is ‘running’. The 011-154 also provides dual inputs for a Series 1000 light curtain and a ‘guard override function. The override facility enables the light curtain’s safety output relays to be negated for a short period. This facility is essential in the packaging industry, for light curtains that are positioned across conveyors that prevent access to personnel but allowing pallet loads to pass through. The monitored safety output relay switches are rated at 250V AC, 2A, for connection to a power-switching device or directly to a machines final control element. Electronic outputs are provided, one for guard status indication and the other for mute indication. The MFU also includes external device monitoring (EDM) and visual indicators on all inputs and outputs. Monitoring between associated input channels ensures the unit is suitable for Category 3 control systems as defined in BS EN 954-1.

MULTIFUNCTION SAFETY UNITS 13

Page 16: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Multifunction Safety Unit Type 011-149

Status Indicators

Function Colour Status

Power Red LED ON when power ON

Inputs Green LED ON when input ON

EDM Amber ON when EDM active

MULTIFUNCTION SAFETY UNITS 14

Page 17: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Features - Type 011-149 q Dual safety inputs for connecting the light curtain q Safety monitored output relays. Contacts rated at 250V AC, 4A q Auxiliary electronic output for status indication etc. q Reset function q External Device Monitor (EDM) q LED status indicators q Din rail mounting - 70mm enclosure q Built to BS EN 954-1 Category 3

Specification - Type 011-149

Response time 10ms max

Operating temperature 0° to +50°C

Enclosure rating IP40

Enclosure 70mm DIN rail mounting (HxWxD) 90x70x60mm

Power supply requirements

24V DC ± 10% reg

Current consumption 100mA (NO LOAD)

Status indicators LEDs, power on + lockout + output Classification BS EN 954-1 Category 3

Electrical connections - Type 011-149 Terminals A1 and A2 – Power supply input - Connect a suitably stabilised 24V DC power supply to terminals A1 = +24V DC and A2 = 0V DC. The current consumption of the MFU with no load applied on the output switching terminals is 100mA.

INPUTS

Dual safety monitored inputs 24V DC = ON, 0V = OFF

External device monitoring (EDM) Use voltage free switch contacts (N/O & N/C)

Reset function (selectable) Use voltage free switch contacts

OUTPUTS

Safety output relays 2 x fail safe change over contacts, each rated at 250V AC, 4A

Auxiliary solid-state switch (non safety)

1 electronic output switch, rated at 24V DC, 500mA

MULTIFUNCTION SAFETY UNITS 15

Note: When in a tripped condition there will be no 24V DC supply to the transmitter head on terminal B1.

Page 18: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Terminal A3 and A4 – Automatic reset mode - Link terminal A3 to terminal A4 if automatic reset is required. In the automatic reset mode no connections are required at terminal B7 and terminal B8. To simplify set-up link A3 to A4. Remove link after set-up if latched

mode is required. Terminals A5 and A6 – External device monitor (EDM) - Auxiliary change over contacts, from an external power-switching device are connected across terminals A5 and A6. The monitoring circuit checks that the power switching devices both de-energise at the same time the MFU safety output switches de-energise. If one of the power switching devices fail to de-energise at this time the MFU will trip. Terminals A7 and A8 – no connections Terminal A9 – Auxiliary electronic switching output - The Auxiliary switching output should only be used for non-safety critical applications. For example connecting an indicator lamp or as feedback to a PLC to the safety outputs have de-energised. The auxiliary output, derived from safety input OSSD2, energises when output switches 1 and 2 energise. Auxiliary output ON = 24V DC and OFF = 0V DC. Terminal A10, A11 and A12 – Safety output 1 switch contacts - Terminals A10, A11 and A12 are the output connections to safety relay 1 changeover switching contacts. Terminal A11 is the common output, with terminal A12 as the normally open switch and A10 as the normally closed switch. Normally, terminals A11 and A12 would be connected to one channel of a machine’s stop circuitry. For example, via an external power-switching relay or directly to a safe PLC input or a machines final control element. Terminals B1 – 24V DC supply- + 24V DC output for connecting to the light curtain Transmitter head (TX).

MULTIFUNCTION SAFETY UNITS 16

Note: If the EDM circuit is not used it is necessary to link terminals A5 to A6 otherwise the system will default into a lockout condition. If connection is missing between A5 & A6 there will be no 24V DC supply to the transmitter head on terminal B1

Page 19: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Terminals B2 – 0V DC supply - 0V DC output for connecting to the light curtain TX. Terminals B3 – 24V DC supply - + 24V DC output for connecting to the light curtain RX. Terminals B4 – 0V DC supply - 0V DC output for connecting to the light curtain RX. Terminal B5 and B6 – light curtain inputs (OSSD1 and OSSD2) Connect the electronic output switches (OSSD1 and OSSD2) of a 1000 Plus Series light curtain to terminals B5 and B6 respectively. Terminals B7 and B8 – Reset - If the MFU is required to be in the latch mode a suitable switch should be connected between terminal B7and terminal B8. If the safety output relays de-energise a depression of the switch is required to re-energise the output switches to an ON condition. The MFU’s safety output switches will only re-energise when the reset switch is depressed and then released. If the MFU is required to operate in an automatic reset condition do not connect a switch to terminals B7 and B8. However, it is necessary to link terminal A3 to terminal A4 before an automatic reset condition can be established. Terminals B9 – No connections Terminal B10, B11 and B12 – Safety output 2 switch contacts - Terminals B10, B11 and B12 are the output connections to safety relay 2 changeover switching contacts. Terminal B11 is the common output, with terminal B12 as the normally open switch and B10 as the normally closed switch. Normally, terminals B11 and B12 would be connected to one channel of a machine’s stop circuitry. For example, via an external power switching relay or, directly to a safe PLC input or to a machines final control element. Connect terminals A5 and A6 to one channel of a machine’s stop circuitry. For example, via an external power-switching relay or, directly to a safe PLC input or a machines final control element.

MULTIFUNCTION SAFETY UNITS 17

Note: If a single channel safety circuit is used link terminals A12 and B11. Terminals A11 and B12 are then connected to the machine’s safety circuit. Connecting in this way links safety output switch 1 and safety output switch 2 in a series configuration.

Page 20: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Multifunction Safety Unit Type 011-150

Status Indicators

Function Colour Status Inputs Green LED ON when input ON

Outputs Green LED ON when output ON

Reset Amber LED ON , when reset input ‘ON (Auto reset mode - LED on continuously)

EDM Amber ON when EDM inputs are active

Status Red + Red Steady ON = system ok Flashing ON /OFF = lockout

MULTIFUNCTION SAFETY UNITS 18

Page 21: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Features - Type 011-150 q Two dual safety inputs for connecting up to 2 light curtains q Dual inputs for connecting the emergency stop circuit q Safety monitored output relays. Contacts rated at 250V AC, 2A q Auxiliary electronic output switches for status indication etc q Reset function q External Device Monitoring (EDM) q LED indicators for all inputs and outputs q DIN rail mounting – 70mm enclosure q Automatic self testing q Simultaneous monitoring between related channels q Built to BS EN 954-1 Category 4 Specification - Type 011-150

Response time 25ms max

Operating temperature 0° to +50°C

Enclosure rating IP40

Enclosure 70mm DIN rail mounting (HxWxD) 90x70x60mm

Power supply 24V DC ± 10% reg

Current consumption 150mA (NO LOAD) Status indicators LEDs for all inputs and outputs Classification BS EN 954-1 Category 4

INPUTS

Dual inputs for light curtain 1 Dual inputs for light curtain 2

24V DC = ON, 0V = OFF - Disparity between related channels = 100ms max.

Dual inputs for emergency-stop circuit

Use voltage free switch contacts - Disparity between channels = 100ms max.

External device monitoring (EDM)

Use voltage free switch contacts (N/C)

Reset function (selectable) 24V DC = ON, 0V = OFF

OUTPUTS

Safety output relays 2 x N/O - fail safe contacts, each rated at 250V AC, 2A

Auxiliary solid-state switches (non safety)

2 electronic output switches, each rated at 24V DC, 500mA

MULTIFUNCTION SAFETY UNITS 19

Page 22: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Electrical connections - Type 011-150 Terminals A1 and A2 – Power supply input - Connect a suitably stabilised 24V DC power supply to terminals A1 = +24V DC and A2 = 0V DC. The current consumption of the MFU with no load applied on the output switching terminals is 150mA. Terminals A3 and A4 – External device monitor (EDM) - Normally closed switch contacts, in series from the external power switching devices are connected across terminals A3 and A4. The monitoring circuit checks that the power switching devices both de-energise at the same time the MFU safety output switches de-energise. If one or both of the power switching devices fail to de-energise at this time the MFU goes into a lockout condition, turning all output switches off. To reset from a lockout condition it is necessary to remove the 24V DC supply from the MFU and then re-apply. If the EDM circuit is not used it is necessary to link terminals A3 to A4 otherwise the system will go to a lockout condition at the next demand upon the safety system. Terminals A5 and A6 – Safety output 1 switch contact - Connect terminals A5 and A6 to one channel of a machine’s stop circuitry. For example, via an external power-switching relay or directly to a safe PLC input or a machines final control element. Terminals A7 and A8 – Safety output 2 switch contact - Connect terminals A7 and A8 to one channel of a machine’s stop circuitry. For example, via an external power-switching relay or directly to a safe PLC input or a machines final control element. If a single channel safety circuit is used link terminals A6 and A7. Terminals A5 and A8 are then connected to the machine’s safety circuit. Connecting in this way links safety output switch 1 and safety output switch 2 in a series configuration. Terminal A9 – No connection Terminal A10 – Auxiliary electronic switching output 1 - The Auxiliary switching output should only be used for non-safety critical

MULTIFUNCTION SAFETY UNITS 20

Page 23: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

application. For example connecting an indicator lamp or as feedback to a PLC to confirm the safety outputs have de-energised. Terminal A11 – Auxiliary electronic switching output 2 - The Auxiliary switching output should only be used for non-safety critical applications. For example connecting an indicator lamp or as feedback to a PLC to confirm the safety outputs have de-energised. Auxiliary outputs 1 and 2 both energise when safety output switches 1 and 2 energise and both de-energise when the safety outputs de-energise. Auxiliary outputs ON = 24V DC and OFF = 0V DC. Terminal A12 – Reset - If the MFU is required to be in the latch mode a suitable switch should be connected between terminal A12 and the 24V DC supply. If the safety output relays de-energise a depression of the switch is required to re-energise the output switches to an ON condition. The MFU’s safety output switches will only re-energise when the reset switch is depressed and then released. If the MFU is required to operate in an automatic reset condition do not connect a switch to terminal A12. However, it is necessary to link terminal A12 to terminal A10 before an automatic reset condition can be established. Terminal B1 and B2 – light curtain 1 inputs (OSSD1 and OSSD2) - Connect the electronic output switches (OSSD1 and OSSD2) of a 1000 Plus Series light curtain to terminals B1 and B2 respectively.

Terminal B3 and B4 – light curtain 2 inputs (OSSD1 and OSSD2) - Connect the electronic output switches (OSSD1 and OSSD2) of a 1000 Plus Series light curtain to terminals B3 and B4 respectively.

MULTIFUNCTION SAFETY UNITS 21

Note: An internal circuit monitors disparity between the two input channels. If the inputs do not switch together (within 100ms of each other) the system will go into a lockout condition.

Note: An internal circuit monitors disparity between the two input channels. If the inputs do not switch together (within 100ms of each other) the system will go into a lockout condition.

Page 24: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Important, if either terminal B1/B2 or, B3/B4 are not used; for example, if only one light curtain is employed for a particular application, it is necessary to link the unused input terminals to the 24V DC supply. If not the MFU’s output switches will not energise. Terminals B5/B6 and B7/B8 – dual channel emergency stop circuit - Connect one channel of the machines emergency stop circuit between terminals B5 and B6 and the second channel between terminals B7 and B8.

Important, if the emergency stop inputs are not used it is necessary to link terminals B5 to B6 and terminals B7 to B8. If not the safety output switches will not energise. Terminals B9 and B11 – 24V DC supply - Additional + 24V DC outputs for connecting to the light curtains etc. Terminals B10 and B12 – 0V DC supply - Additional 0V DC outputs for connecting to the light curtains etc.

MULTIFUNCTION SAFETY UNITS 22

Note: An internal circuit monitors for short circuits and switching disparity between the two input channels. If the inputs do not switch together (within 100ms of each other) the system will go into a lockout condition. This configuration meets the requirements for ‘control reliability’ and cannot be used in a single channel configuration.

Page 25: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Multifunction Safety Unit Type 011-151

Status Indicators

Function Colour Status Inputs Green LED ON when input ON

Outputs Green LED ON when output ON Reset Amber LED ON , when reset input is ‘ON EDM Amber ON when EDM inputs are active

Status Red + Red Steady ON = system ok Flashing ON /OFF = lockout

MULTIFUNCTION SAFETY UNITS 23

Page 26: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Features - Type 011-151 q Dual safety inputs for connecting the light curtain q Dual inputs for muting the light curtain q Dual inputs for connecting the emergency stop circuit q Safety monitored output relays. Contacts rated at 250V AC, 2A q Auxiliary electronic output for mute indication q Reset function q External Device Monitoring (EDM) q LED indicators for all inputs and outputs q DIN rail mounting – 70mm enclosure q Automatic self testing q Monitoring between related channels q Built to BS EN 954-1 Category 3 Specification - Type 011-151

Response time 25ms max Operating temperature 0° to +50°C Enclosure rating IP40

Enclosure 70mm DIN rail mounting (HxWxD) 90x70x60mm

Power supply requirement 24V DC ± 10% reg Current consumption 150mA (NO LOAD) Status indicators LEDs for all inputs and outputs Classification BS EN 954-1 Category 3

INPUTS

Dual inputs for light curtain 24V DC = ON, 0V = OFF - Disparity between channels =500ms max.

Dual inputs for mute sensors 24V DC = ON, 0V = OFF - Disparity between channels =10 secs. max.

Dual inputs for emergency-stop circuit

Use voltage free switch contacts - Disparity between channels =100 ms max.

External device monitoring (EDM) Use voltage free switch contacts (N/C) Reset function (selectable) 24V DC = ON, 0V = OFF

OUTPUTS

Safety output relays 2 x N/O - fail safe contacts, each rated at 250V AC, 2A

Auxiliary solid-state switch (non safety)

Electronic output switch, rated at 24V DC, 500mA

Auxiliary solid-state switch for mute indication

Electronic output switch, rated at 24V DC, 500mA

MULTIFUNCTION SAFETY UNITS 24

Page 27: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Electrical connections – MFU 011-151 Terminals A1 and A2 – Power supply input - Connect a suitably stabilised 24V DC power supply to terminals A1 = +24V DC and A2

= 0V DC. The current consumption of the MFU with no load applied on the output switching terminals is 150mA.

Terminals A3 and A4 – External device monitor (EDM) - Normally closed switch contacts, in series from the external power switching devices are connected across terminals A3 and A4. The monitoring circuit checks that the power switching devices both de-energise at the same time the MFU safety output switches de-energise. If one or both of the power switching devices fail to de-energise at this time the MFU goes into a lockout condition, turning all output switches off. To reset from a lockout condition it is necessary to remove the 24V DC supply from the MFU and then re-apply. If the EDM circuit is not used it is necessary to link terminals A3 to A4 otherwise the system will go to a lockout condition at the next demand upon the safety system. Terminals A5 and A6 – Safety output 1 switch contact - Connect terminals A5 and A6 to one channel of a machine’s stop circuitry. For example, via an external power-switching relay or directly to a safe PLC input or a machines final control element. Terminals A7 and A8 – Safety output 2 switch contact - Connect terminals A7 and A8 to one channel of a machine’s stop circuitry. For example, via an external power-switching relay or directly to a safe PLC input or a machines final control element. If a single channel safety circuit is used link terminals A6 and A7. Terminals A5 and A8 are then connected to the machine’s safety circuit. Connecting in this way links safety output switch 1 and safety output switch 2 in a series configuration. Terminal A9 – No connection

MULTIFUNCTION SAFETY UNITS 25

Page 28: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Terminal A10 – Auxiliary electronic switching output 1 - The Auxiliary switching output should only be used for non-safety critical application. For example connecting an indicator lamp or as feedback to a PLC to confirm the safety outputs have de-energised. The auxiliary output energises when safety output switches 1 and 2 energise and de-energises when the safety outputs de-energise. Auxiliary output ON = 24V DC and OFF = 0V DC. Terminal A11 – Auxiliary electronic switch – (mute out). The Auxiliary switching circuit energises when the light curtain is muted, e.g. when suitable signals have been applied to terminals B3 and B4. The output switch is normally used for connecting an indicator lamp or as feedback to a PLC to confirm safety light curtain inputs at terminals B1 and B2 are overridden e.g. in a muted condition. Terminal A12 – Reset - A suitable switch should be connected between terminal A12 and the 24V DC supply. If the safety output relays de-energise a depression of the switch is required to re-energise the output switches to an ON condition. The MFU’s safety output switches will only re-energise when the reset switch is depressed and then released. Terminal B1 and B2 – light curtain inputs (OSSD1 and OSSD2) Connect the electronic output switches (OSSD1 and OSSD2) of a light curtain to terminals B1 and B2 respectively.

Important: If terminal B1/B2 are not used it is necessary to link them to the 24V DC supply. If not the MFU’s output switches will not energise. Terminal B3 and B4 – mute input signals - Connect suitable mute initiating signals to terminals B3 and B4 respectively. The mute signals override the light curtains operation therefore, the inputs should only be active during safe periods of the machinery’s operating cycle.

MULTIFUNCTION SAFETY UNITS 26

Note: An internal circuit monitors disparity between the two input channels. If the inputs do not switch together (within 500ms of each other) the system will go into a lockout condition.

Note: An internal circuit monitors disparity between the two mute input channels. If the inputs do not switch within 10 secs. of each other the system will go into a lockout condition.

Page 29: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Terminals B5/B6 and B7/B8 – dual channel emergency stop circuit - Connect one channel of the machines emergency stop circuit between terminals B5 and B6 and the second channel between terminals B7 and B8.

Important, if the emergency stop inputs are not used; it is necessary to link terminals B5 to B6 and terminals B7 to B8. If not the safety output switches will not energise. Terminals B9 and B11 – 24V DC supply - Additional + 24V DC outputs for connecting to the light curtains etc. Terminals B10 and B12 – 0V DC supply - Additional 0V DC outputs for connecting to the light curtains etc.

MULTIFUNCTION SAFETY UNITS 27

Note: An internal circuit monitors for short circuits and switching disparity between the two input channels. If the inputs do not switch together (within 100ms of each other) the system will go into a lockout condition. This configuration meets the requirements for ‘control reliability’ and cannot be used in a single channel configuration.

Page 30: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Multifunction Safety Unit Type 011-153

Status Indicators

Function Colour Status K1 ON Green LED ON with power to K1 coil K2 ON Green LED ON with power to K2 coil

MULTIFUNCTION SAFETY UNITS 28

Page 31: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Features - Type 011-153 q Positive guided contacts (8 N/O + 2 N/C) q Din rail mounting - 70mm enclosure q LED status indication q Feedback control loop connections q Built to BS EN 954-1 Category 4

Specification - Type 011-153

Response time 10ms max Operating temperature -10° to +55°C Enclosure rating IP40 Enclosure 70mm DIN rail mounting

(HxWxD) 90x70x60mm Power supply requirement 24V DC ± 10% reg Status indicators LEDs Relay Power on Classification BS EN 954-1 Category 4 Contact switching capability 24V DC / 250V AC

0.01A - 4A Maximum total output current 26A

The expansion module operates in conjunction with MFU’s 011-149, 011-150, 011-151 and 011-154 to provide additional output switching contacts that may be required for a particular application.

MULTIFUNCTION SAFETY UNITS

29

Page 32: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Electrical connections – Type 011-153 Terminal A1 – Input connection from a safe output device to the relay coil of K1 (+24V DC) Terminal B1 - Power supply input to the relay coil of K1 (0V DC) Terminal A2 - Power supply input to the relay coil of K2 (+24V DC) Terminal B2 – Input connection from a safe output device to the relay coil of K2 (0V DC) Terminals A3 to A10 and terminal B3 to B10 – Total of 8 N/O safe output switching contacts each contact rated at 250V AC 4A. Terminals A11, B11, A12 and B12 – 2 N/C output switching contacts each contact rated at 250V AC 4A. One of the N/C contacts can be used as feedback connections to the External Device Monitor associated with MFU types 011-150 and 011-151. One N/C contact in conjunction with one of the N/O contacts can be used as feedback connections to the External Device Monitor associated with MFU type 011-149.

MULTIFUNCTION SAFETY UNITS 30

Page 33: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Multifunction Safety Unit Type 011-154

Status Indicators

Function Colour Status Inputs Green LED ON when input ON

Outputs Green LED ON when output ON Reset Amber LED ON , when reset input is ON Guard

override Green LED ON, when override input is ON

EDM Amber ON when EDM inputs are active

Status Red + Red Steady ON = lockout Flashing ON /OFF = system ok

MULTIFUNCTION SAFETY UNITS

31

Page 34: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Features - Type 011-154 q Dual safety inputs for connecting the light curtain q Dual inputs for muting the light curtain q 3rd mute input (mute enable) for increased safety integrity q Safety monitored output relays. Contacts rated at 250V AC, 2A q Monitored electronic output for mute indication q Reset control function q External Device Monitoring (EDM) q LED indicators for all inputs and outputs q Guard override function q Electronic output for guard status indication q Simultaneous monitoring between related channels q Built to BS EN 954-1 Category 3 Specification - Type 011-154 Response time 25ms max Operating temperature 0° to +50°C Enclosure rating IP40

Enclosure 70mm DIN rail mounting (HxWxD) 90x70x60mm

Power supply requirement 24V DC ± 10% reg Current consumption 150mA (NO LOAD) Status indicators LEDs for all inputs and outputs Classification BS EN 954-1 Category 3 INPUTS

Dual inputs for light curtain 24V DC = ON, 0V = OFF - Disparity between channels =500ms max.

Dual inputs for mute sensors 24V DC = ON, 0V = OFF - Disparity between channels =10 secs. max.

3rd mute input (mute enable) 24V DC = ON, 0V = OFF External device monitoring (EDM) Use voltage free switch contacts (N/C) Reset function 24V DC = ON, 0V = OFF Override function 24V DC = ON, 0V = OFF (3 min time-out) OUTPUTS

Safety output relays 2 x N/O - fail safe contacts, each rated at 250V AC, 2A

Auxiliary solid-state switch (non safety)

Electronic output switch, rated at 24V DC, 500mA

Monitored solid-state switch for mute indication

Electronic output switch, rated at 24V DC, 500mA

MULTIFUNCTION SAFETY UNITS 32

Page 35: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Electrical connections – MFU 011-154 Terminals A1 and A2 – Power supply input - Connect a suitably stabilised 24V DC power supply to terminals A1 = +24V DC and A2 = 0V DC. The current consumption of the MFU with no load applied on the output switching terminals is 150mA. Terminals A3 and A4 – External device monitor (EDM) - Normally closed switch contacts, in series from the external power switching devices are connected across terminals A3 and A4. The monitoring circuit checks that the power switching devices both de-energise at the same time the MFU safety output switches de-energise. If one or both of the power switching devices fail to de-energise at this time the MFU goes into a lockout condition, turning all output switches off. To reset from a lockout condition it is necessary to remove the 24V DC supply from the MFU and then re-apply. If the EDM circuit is not used it is necessary to link terminals A3 to A4 otherwise the system will go to a lockout condition at the next demand upon the safety system. Terminals A5 and A6 – Safety output 1 switch contact - Connect terminals A5 and A6 to one channel of a machine’s stop circuitry. For example, via an external power-switching relay or directly to a safe PLC input or a machines final control element – refer to drawing (E) above Terminals A7 and A8 – Safety output 2 switch contact - Connect terminals A7 and A8 to one channel of a machine’s stop circuitry. For example, via an external power-switching relay or directly to a safe PLC input or a machines final control element - refer to drawing (E) above.

MULTIFUNCTION SAFETY UNITS

33

Page 36: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

If a single channel safety circuit is used link terminals A6 and A7. Terminals A5 and A8 are then connected to the machine’s safety circuit. Connecting in this way links safety output switch 1 and safety output switch 2 in a series configuration. Terminal A9 – No connection Terminal A10 – Auxiliary electronic switching output 1 - The Auxiliary switching output should only be used for non-safety critical application. For example connecting an indicator lamp or as feedback to a PLC to confirm the safety outputs have de-energised. The auxiliary output is on when OSSD 1 and 2 energise. They are off when OSSD 1 and 2 are de-energised. Auxiliary output ON = 24V DC and OFF = 0V DC. Terminal A11 – Monitored electronic switch – (mute out). A monitored switching circuit energises when the light curtain is in a muted condition, e.g. when suitable signals have been applied to terminals B3 and B4. This output is for connection of a 24V DC 2.2W filament lamp. The lamp will illuminate when the light curtain is in a muted condition.

Terminal A12 – Reset - A suitable switch should be connected between terminal A12 and the 24V DC supply. If the safety output relays de-energise then a depression of the switch is required to re-energise the output switches to an ON condition. The MFU’s safety output switches will only re-energise when the reset switch is depressed and then released. Terminal B1 and B2 – light curtain inputs (OSSD1 and OSSD2)

- Connect the electronic output switches (OSSD1 and OSSD2) of a light curtain to terminals B1 and B2 respectively.

MULTIFUNCTION SAFETY UNITS 34

Warning: The system must have a 24V, 2.2 watt filament lamp connected between A11 and 0V for the system to work.

Note: An internal circuit monitors disparity between the two input channels. If the inputs do not switch within 500ms of each other then the system will go into a lockout condition.

Page 37: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Terminal B3 and B4 – mute input signals - Connect suitable mute initiating signals to terminals B3 and B4 respectively. The mute signals override the light curtains operation therefore, the inputs should only be active during safe periods of the machinery’s operating cycle.

Terminals B5 – 3rd mute input (mute enable) For additional safety integrity a third mute input signal is provided. For entry/exit applications the input is normally connected to a conveyor ‘run’ signal thus, initiating a mute condition only when the appropriate conveyor is running. Link terminal B5 to 24V dc if the third mute input is not required. Terminal B6 – no connection Terminal B7 – Guard override Should the guard trip during a period when a pallet is transferring through the light curtain detection zone it is necessary to remove the load from the zone before the light curtain can be reset. Install the guard override function by connecting a N/O key or, push button switch between terminal B7 and +24V dc. The override function can only be operated if a pallet load is obstructing the detection zone and the light curtain is in a tripped condition. Operate the override function as follows: Activate and release the override switch. This will automatically mute the light curtain for a maximum period of three minutes or, until the light curtain detection zone has been cleared of the obstruction. If the latter then, as the pallet load passes out from the light curtain the override function is cancelled and the guard becomes fully active once again, without interrupting the machine operating cycle.

MULTIFUNCTION SAFETY UNITS

35

Note: An internal circuit monitors disparity between switching of the two mute input channels. If the inputs do not respond within 2 seconds. of each other the system will trip.

To satisfy the latest Health and Safety requirements the safety system will trip if the light curtain remains in a muted condition for more than 15 minutes.

Page 38: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Terminals B9 and B11 – 24V DC supply - Additional + 24V DC outputs for connecting to the light curtains etc. Terminals B10 and B12 – 0V DC supply - Additional 0V DC outputs for connecting to the light curtains etc.

MULTIFUNCTION SAFETY UNITS 36

Page 39: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Mounting Kit

Model number

Description

011-130 Mounting bracket kit

4 x 'L' shaped stainless steel mounting brackets and a set of M6 x 8mm screws.

ACCESSORIES

37

For fixing centres 36mm + (m)mm For (m) see product tables on page 8, 9 & 10

Page 40: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

1000 Series Reset Station The 1000 Series reset station provides the user with a guard reset function and guard status indication. Mounted in a robust enclosure with a bright LED lamp and 6mm screw size mounting brackets top and bottom. Each unit comes with an integrated 10m connection cable for interface via a 1000 Series multi function unit (MFU), 011-149, 011-150 or 011-151

Model number Description

011-302 1000 Series push button reset station with trip indication

ACCESSORIES 38

Page 41: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Power Supplies

If a suitable stabilised 24V DC 2.5A power supply is not available the following unit is recommended. A 24V DC 1A power supply option is also available.

Features q High reliability q High efficiency, low working temp q Built in EMI filter, low ripple noise q Compact size, lightweight q Short circuit, over load, over voltage protection Approvals: UL, TUV, CB and CE

Specification 071-050

Specification 071-040

Model number Description

071-050 Power supply Input 85 - 264V AC Output 24V DC, 2.5A

071-040 Power supply Input 100 – 240V AC Output 24V DC, 1.1A

Type Switch mode Input Voltage 85 - 264V AC Input frequency 47-63HZ Inrush current Cold start, 24A, 115V & 50A, 230V Output voltage/current rating 24V DC, 2.5A Operating temperature 0°C to 50°C Storage temperature -10°C to +70°C Connection 5P/9.5mm pitch terminal block Enclosure 160x98x38mm Din rail mounting Weight 0.5 Kg

Type Switch mode Input Voltage 100 - 240V AC Input frequency 50-60HZ Inrush current Cold start, 15A, 115V & 30A, 230V Output voltage/current rating 24V DC, 1.1A Operating temperature 0°C to 50°C Storage temperature -10°C to +70°C Connection 5P/9.5mm pitch terminal block Enclosure 99x97x35mm Din rail mounting Weight 0.37 Kg

ACCESSORIES

39

Page 42: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Mirror Units Two or three sides of a machine can be safeguarded with a single light curtain by using mirrors to deflect the light curtain’s infra-red beams. (see appendix 2 for installation guidance)

The Smartscan mirror system provides a sturdy floor mounting kit togethr with an aluminium column for mounting the mirror. The mirror assembly simply slots onto the column and can be adjusted to the height required for the application.

The special mounting stand enables the mirror unit to be rotated through 360 degrees while also allowing full adjustment in all axes.

ACCESSORIES 40

Note: Mirrors cause a reduction in optical efficiency, reducing the effective range of the light curtain. Refer to appendix 2 for guidance.

Page 43: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Range of the light curtain

Maximum range through 1 mirror

Maximum range through 2 mirrors

0.5m - 5m 4m 3m 4m -10m 8m 6.5m

Model number Description

044-252 600mm x 110mm wide mirror unit 044-249 900mm x 110mm wide mirror unit 044-250 1200mm x 110mm wide mirror unit 044-253 1400mm x 110mm wide mirror unit

Column & Floor Stand

Model number Description

044-256 1.1m aluminium universal mounting column 044-257 1.3m aluminium universal mounting column 044-258 1.6m aluminium universal mounting column 044-247 1.8m aluminium universal mounting column 044-262 2.0m aluminium universal mounting column 044-248 Floor stand

ACCESSORIES

41

Note: Mirror length must be a minimum of 100mm longer than the overall length of the light curtain to be installed.

Note: A universal mounting column and floor stand is required for each mirror unit.

Page 44: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Mute signalling photocell Type 011-140 The polarised retro-reflective photocell can be used in conjunction with MFU 011-151 to provide the mute initiating signals to terminals B3 and B4 of the MFU. A safety light curtain with mute control function is often used in the packaging industry. In conjunction with a 1000 Series light curtain and an MFU 011-151 two photocells are positioned to scan across a conveyor, to detect loaded pallets prior to the load interrupting the light curtain. The photocell must be positioned to detect the load during the entire time the load is passing through the light curtain. Type 011-140 photocell has a maximum sensing range of 3 metres. Each photocell comes complete with mounting bracket and retro-reflective mirror.

Model number

Description

011-140 Polarised retro reflective photocell kit

Sensing Distance 10m Transmitter Diode Infrared Sensing Adjustment None Protection Rating IP65 Operating Voltage 12-240V dc, 24-240V ac - 50/60Hz Output Relay Current Consumption 2VA max Response Time 15ms Enclosure Intensive ABS Cable 1.5m length Operating Temp -20°C to +60°C Humidity 35% to 85% Weight 285g

ACCESSORIES 42

(each kit contains 1x photocell, 1x reflector mirror, 1x mounting bracket)

Page 45: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Mute Signalling Photocell Type 011 - 141 The through-beam infra-red photocell can be used in conjunction with MFU 011-151 to provide the mute initiating signals to terminals B3 and B4 of the MFU.

A safety light curtain with mute control function is often used in the packaging industry. In conjunction with a 1000 Series light curtain and an MFU 011-151 two photocells are positioned to scan across a conveyor, to detect loaded pallets prior to the load interrupting the light curtain. The photocells are positioned to scan across a conveyor, to detect loaded pallets prior to the load interrupting the light curtain. Type 011 - 141 photocells have a maximum sensing range of 10 metres. Each transmitter and receiver comes complete with a 1.5m cable.

Model number

Description

011 - 141 Through-beam photocell kit

Sensing Distance 10m Transmitter Diode Infrared Sensing Adjustment None Protection Rating IP65 Operating Voltage 12-240V dc, 24-240V ac - 50/60Hz Output Relay Current Consumption 2VA max Response Time 15ms Enclosure Intensive ABS Cable 1.5m length Operating Temp -20°C to +60°C Humidity 35% to 85% Weight 285g

ACCESSORIES

43

(each sensor kit contains 1x Transmitter unit , 1x Receiver unit, Mounting brackets)

Page 46: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Smartscan Remote Mounting Stackable Beacons

Remote Mounting Stackable Beacons A range of Stackable Beacons are available. They are typically used where the machine application requires visual indication of control functions from a single location. The translucent plastic lenses provide all round light visibility and can be programmed to provide either flashing or a steady output. The bright LED’s are supplied in a variety of colours as listed below.

Mounting Stands Designed to accommodate our range of safety light curtains. The Adjustable Stand (50mm x 50mm) offers the user a flexible mounting option. The stand has adjustable brackets that allow the safety light curtain to be mounted at different positions to suit a specific application. Brackets for mounting mute signalling photocells on the stand are also available. The Channel Stand allows the user to mount the safety light curtain inside a protective housing. This provides protection on three sides to give a more robust installation. Channel stands would typically be used where the safety light curtain is at risk of damage from fork lift truck operations, or in the case of end-of-line applications damage from falling pallet loads.

Model number Description

105 - 801 High intensity LED stackable beacon kit - Red 105 - 802 High intensity LED stackable beacon kit - Orange 105 - 803 High intensity LED stackable beacon kit - Green 105 - 804 High intensity LED stackable beacon kit - Blue 105 - 810 Monitored mute beacon module

ACCESSORIES 44

Page 47: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Adjustable Mounting Stands

Straight stands

Model number

Description Height

044 – 408 Pair of adjustable straight stands (with complete bracket set) 2m

ACCESSORIES

45

Page 48: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

L stands (exit systems)

Model number

Description Height

044 - 412 Pair of adjustable ‘L’ style stands (with external mute sensor bracket sets) 2m

ACCESSORIES 46

044 - 412

Page 49: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

T stands (entry / exit systems)

Model number

Description Height

044 - 400 Pair of adjustable ‘T’ style stands (with external mute sensor bracket set) 2m

ACCESSORIES

47

044 - 400

Page 50: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Channel Mounting Stands

Straight stands

Model number Description Height

044 - 118 Pair of channel floor stands (straight) 1.5m 044 – 218 Pair of channel floor stands (straight) 2m

ACCESSORIES 48

Page 51: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Safety System Solutions

Smartscan recognise the difficult balance that customers have to make between meeting Health & Safety legislation requirements and managing their demanding production needs. Smartscan design and manufacture systems to meet the particular needs of their customer’s safety applications - from single machines to full production lines. We provide our customers with a total service, from initial safety advice through to regular maintenance of their safety systems.

Expert Advice Risk Assessment Safety System Design Product Specification Safety System Installation System Maintenance

SAFETY SYSTEMS SOLUTIONS

49

Page 52: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Installation Sheet Number CD205/290305

Unpacking q Remove all packaging material and retain it q Locate and keep the delivery note q Inspect all items for transit damage q Match goods supplied to those specified on the delivery note q Keep the Installation Sheet in a safe place

Each 1000 Plus system supplied would normally include: q Light curtain with 5m of cable attached to transmitter and

receiver columns q Test piece q Installation sheet q Service questionnaire form Storage requirements q Humidity - <95% q Temperature range between –20°C and +70°C

INSTALLATION SHEET 50

Page 53: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Operating Requirements q Humidity <95% q Temperature range between 0°C and 50°C q Vibration: Frequency <55Hz Max. Movement <0.35mm q Do not use equipment in explosive atmospheres, (contact the

manufacturer for further advice)

Fig. B also describes important parameters associated with the light curtain. Those parameters are shown as M, K, R and N.

M – Overall length of light curtain enclosures K – Detection zone width R – Minimum and maximum scanning ranges of the light curtain

N – Object Detection Capability. (The minimum size of object guaranteed to be detected when placed in the light curtain energy field.)

INSTALLATION SHEET

51

Page 54: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Typical Mounting Arrangement for a Smartscan 1000 Plus

The 1000 Plus Series system does not use cable connectors. Both the transmitter and receiver units come complete with 5m cables attached. Transmitter = 2 way cable, Receiver = 4 way cable. The 1000 Plus Series has a unique mounting arrangement. Threaded slots running from top to bottom of the transmitter and receiver columns enable M6 screws to be affixed at any position along the length of the slot. The M6 threaded slots run the entire length of the aluminium extrusion, between the two end caps. There is a slot at each side of the extrusion and two slots at the rear as shown in Fig. C.

INSTALLATION SHEET 52

Note: As an additional option a Mounting Bracket Kit (011-130) is available.

Page 55: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Detection zone width (K) - Must be of a suitable height for each application to prevent personnel access to the danger area either over, under or around the light curtains detection zone. Detection capability (N) - A test piece of appropriate size is provided to test that the light curtain object detection capability is within the parameter specified for the particular model number. Range (R) - Ensure the light curtain is capable of satisfying the range requirement for the application.

INSTALLATION SHEET

53

Page 56: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

When installing a Smartscan 1000 Plus Series light curtain your attention is drawn to the following: (Fig. E) 1. Consider reflective surfaces that may give rise to optically ‘short

circuiting’ the direct path of the light curtains as shown in Fig. E. To ensure the light curtain is mounted far enough away from reflective surfaces use the formulae provided to calculate the minimum dimension between the light curtain and reflective surface.

X = minimum distance between reflective surface and light curtain.

2. To prevent intermittent tripping of the light curtain ensure

extraneous infra red energy between 800 and 1000 nanometers is not directed towards the Perspex window of the receiver unit (RX). Extraneous sources would include infra red sensors, infra-red remote controls or scanning systems.

3. Ensure the mounting position of

the light curtain in respect to the nearest danger point meets the requirements of European Standard BS EN 999. See Appendix 1.

4. Ensure the light curtain transmitter

and receiver units are mounted accurately in line with each other and are both perpendicular and parallel to each other within the parameters shown for each axis.

5. If utilising mirrors to deflect the light

curtain ensure the mirror length is 100mm longer than the light curtain detection zone width and, mounted centrally to the zone. To ensure reliable operation the light curtain deflection angle from the mirror must not be less than 40 degrees or greater than 100 degrees.

INSTALLATION SHEET 54

Page 57: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Fig. F shows examples of the identification labels that are affixed to the end cap at the bottom of the transmitter and receiver columns.

INSTALLATION SHEET

55

Page 58: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Fig. G defines the features (F) associated with the Smartscan 1000 system.

LED Status Indicators F1 - Yellow ‘flashing’ indicators on the (TX) transmitter column indicates the unit is powered-up and the electronic system is operational. F2 - Yellow ‘flashing’ indicators on the (RX) receiver column indicates that communication is established between transmitter and receiver, and the light curtain is correctly aligned. Yellow ‘steady’ indicators on the (RX) receiver column indicates that the light curtain is incorrectly aligned or the light curtain detection zone is ‘blocked’. F3 - Green LED indicator at the receiver unit illuminates when the electronic output switches, OSSD1 and OSSD2 are ‘ON’ (only when the light curtain detection zone is ‘clear’ of any obstruction). F4 - Red LED indicator at the RX unit illuminates when the electronic output switches, OSSD1 and OSSD2 are ‘OFF’ eg a trip condition or, when the light curtain detection zone is ‘blocked’. If the Red LED indicator is flashing the system is in lockout. To recover from a lockout condition disconnect the transmitter and receiver from the power source and then reapply. F6 - Output Signal Switching Devices OSSD1 and OSSD2 provide the fail-safe signals for switching a safe control relay or electrical contactor. Both output signals are termed, ‘control reliable’; the transistor output switches are automatically turned ‘OFF’ for a very brief period of time to enable the electronic safety system to automatically self check thus ensuring the switches are able to turn OFF permanently if required to do so. This function increases the

INSTALLATION SHEET 56

Page 59: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

safety integrity of the Smartscan 1000 Plus system to a very high level. The switching period is so short (500 µs max.) that it has no effect on the output signal to the machine safety circuits, thus the machine will continue to operate during the automatic test periods.

Note: The standing current for each OSSD should be no less the 20mA and no greater than 500 mA

INSTALLATION SHEET

57

Page 60: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Fig. H shows the 1000 Plus light curtain model list, showing part codes, detection zone width (K) and weight in Kg of transmitter and receiver columns.

INSTALLATION SHEET 58

Note: Perimeter guards have a 6 beam unit at the beam locations.

Page 61: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Input and Output Connections at the Transmitter and Receiver Units

A 24V DC regulated power supply should be used for connection to the transmitter and receiver units. The transmitter and receiver units operate entirely independently from each other, e.g. there are no electrical connections between the transmitter and receiver units therefore separate 24V DC power supplies may be used if required. In order to protect the 1000 Series electronic

system please remember to install fuses of suitable rating between incoming 24V DC supply and 24V input connections at both the transmitter and receiver units. Recommended fuse ratings, transmitter 0.5A and receiver 1.5A.

OSSD1 and OSSD2 - Each output switch has a maximum current rating of 0.5A. To prevent possible damage never exceed the maximum current rating for the switching devices.

Ensure both transmitter and receiver units are connected to GROUND. Insert an M6 bolt into one of the threaded slots in the extrusion to ensure a good ground connection.

INSTALLATION SHEET

59

Note: Inductive load suppressors should be used when driving large power relays.

In applications where there may be high levels of EMC interference or where the cables from the Smartscan receiver unit have been extended it is recommended that the clip-on Ferrite EMI suppressor provided is clamped to the receiver cable. For details refer to the installation sheet supplied with each suppressor.

Page 62: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Glossary of words and terminology used in the Installation Sheet in a number of International languages:

INSTALLATION SHEET 60

Page 63: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Testing the light curtain with the test piece The test procedure should be carried out frequently as indicated by the risk assessment for the particular installation. Smartscan Ltd recommends the test should be carried out daily. For light curtains with ODC (N) 30mm and 40mm - refer toFig.L Power-up the light curtain and activate the output switching circuits to an ON condition. Insert a test piece of appropriate size into the light curtain detection zone, at the bottom, 150mm from the transmitter unit. At this point the output switches will turn OFF. Sweep the test piece up through the detection zone parallel to the transmitter. Now sweep the test piece down through the detection zone equal distance between the transmitter and receiver. Now sweep the test piece up through the detection zone 150mm and parallel to the receiver unit. At no time during these tests should the output switches turn ON. Now thrust the test piece anywhere in the light curtain detection zone and ensure the machinery stops without apparent delay. For light curtain models with an ODC above 40mm undertake the same tests as described. During these tests the output switches should only turn OFF as the test piece totally obscures each beam in the light curtain. Ensure that while the test piece is obscuring each beam the output switches are OFF.

INSTALLATION SHEET 61

Page 64: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Routine Maintenance No routine maintenance is required beyond periodic cleaning of the transmitter and receiver windows. Dirt build up on the windows may lead to intermittent tripping or a totally blocked condition of the light curtain. Clear adhesive tape may be applied to the windows of curtains in dirty or abrasive conditions. Renew the clear adhesive tape periodically. Clean the windows with a clean damp cloth using a mild detergent. Never use abrasive, corrosive cleaners or spray detergents. Fig. M shows an operations chart for the 1000 Plus system. Before installation read and understand the Installation Sheet provided paying particular attention to the information provided in Fig. E

q Refer to Fig. L for test

and maintenance procedures

q Every 24 hours carry

out tests as indicated in Fig. L

q Every 6 months check

the entire installation paying particular attention to Fig. E

q If the equipment fails to

operate as intended check the electrical connections as shown in Fig. J

INSTALLATION SHEET 62

Page 65: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Fig. N outlines the procedure for returning a Smartscan product.

If a fault occurs that cannot be resolved or the equipment is damaged return the system to the nearest Smartscan distributor or Smartscan Ltd. Indicate the nature of the fault and the symptoms displayed on the form provided.

INSTALLATION SHEET

63

Note: Please ensure that returned guards are matching serial number pairs.

Page 66: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Fig. P – shows a copy of the declaration of conformity.

INSTALLATION SHEET 64

Page 67: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Positioning the light curtain The following points should be considered before final selection of a light curtain. q The position of the light curtain in relation to the danger point,

particularly the separation distance (S) q The stopping performance of the machine together with the

response time of the safety system (t1 + t2) To assist with the selection of a Smartscan light curtain for a specific application refer to the following information which has been taken from European Standard BS EN 999. Detection capability - the dimension representing the minimum diameter of an opaque cylinder which, when placed into the light curtain, at any angle to the detection plane, is guaranteed to actuate the light curtain. Separation distance (S) - The distance along the direction of approach, between the outermost position at which an appropriate opaque object is detected and the nearest hazardous part. Abbreviations: S = separation distance (mm) H = height of the light curtain above the reference plane (mm) e.g. floor t1 = response time of light curtain and control unit (secs) t2 = stop time of machine (secs) The detection zone of the selected light curtains must be of a length to prevent access to the hazard from either over or underneath the light curtain. If necessary install additional mechanical guarding to prevent access into the hazardous area.

APPENDIX 1

65

Page 68: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Normal Approach

Example for normal approach Using a light curtain with a 30mm detection capability Where the response time of the safety system (t1) = 0.025 secs Where the stopping time of the machine (t2) = 0.05 secs Therefore (t1+t2) = 0.075 secs S = 2000 x 0.075 + 128 S = 278mm

To calculate separation distance (S) Detection Capability

(mm)

Use a formula below when

(t1+ t2) is less than 0.185 secs

Use a formula below when (t1+ t2) is greater than 0.185 secs

30 2000(t1+t2)+128 1600(t1+t2)+128 40 2000(t1+t2)+208 1600(t1+t2)+208

2 or 3 beam light curtains

1600(t1+t2)+850 1600(t1+t2)+850

APPENDIX 1 66

Page 69: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Normal Approach Separation distance (S) in mm Total response time of

machine and safety system (t1 + t2)

Detection capability of the light curtain

ms secs (30) mm (40) mm 2, 3 & 4 beam systems 50 0.050 228 308 930 55 0.055 238 318 938 60 0.060 248 328 946 65 0.065 258 338 954 70 0.070 268 348 962 75 0.075 278 358 970 80 0.080 288 368 978 85 0.085 298 378 986 90 0.090 308 388 994 95 0.095 318 398 1002

100 0.100 328 408 1010 105 0.105 338 418 1018 110 0.110 348 428 1026 115 0.115 358 438 1034 120 0.120 368 448 1042 125 0.125 378 458 1050 130 0.130 388 468 1058 135 0.135 398 478 1066 140 0.140 408 488 1074 145 0.145 418 498 1082 150 0.150 428 500 1090 155 0.155 438 500 1098 160 0.160 448 500 1106 165 0.165 458 500 1114 170 0.170 468 500 1122 175 0.175 478 500 1130 180 0.180 488 500 1138 185 0.185 498 500 1146 190 0.190 500 512 1154 195 0.195 500 520 1162 200 0.200 500 528 1170 205 0.205 500 536 1178 210 0.210 500 544 1186 215 0.215 500 552 1194 220 0.220 500 560 1202 225 0.225 500 568 1210 230 0.230 500 576 1218 235 0.235 504 584 1226 240 0.240 512 592 1234 245 0.245 520 600 1242 250 0.250 528 608 1250 255 0.255 536 616 1258 260 0.260 544 624 1266 265 0.265 552 632 1274 270 0.270 560 640 1282 275 0.275 568 648 1290 280 0.280 576 656 1298 285 0.285 584 664 1306 290 0.290 592 672 1314 295 0.295 600 680 1322 300 0.300 608 688 1330

APPENDIX 1

67

Page 70: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Parallel Approach

To calculate separation distance (S) S = 1600(t1+ t2) + (1200 - (0.4 x H))

The detection capability of a parallel approach light curtain determines the lowest permissible mounting height between the curtain and reference plane (H) e.g.

floor. Refer to the guidance below

Detection capability

(mm)

Lowest allowable height of the light curtain above the reference plane (H) e.g. floor

30 (H) = Any height above the reference plane providing safety can be maintained

40 (H) = Any height above the reference plane providing safety can be maintained

Example for parallel approach The light curtain to be mounted 750mm from the floor (H) Using a light curtain with a 40mm detection capability Where the response time of the safety system (t1) = 0.025 secs] Where the stop time of the machine (t2) = 0.08 secs Therefore (t1 + t2) = 0.105 secs S = 1600 x 0.105 + (1200 - (0.4 x 750)) S = 168 + 1200 - 300 S = 1068mm

APPENDIX 1 68

Page 71: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Parallel Approach

Total response time of machine and safety

systems (t1 + t2)

Separation distance where (H) = 750mm

ms secs (S) in mm 50 0.050 980 55 0.055 988 60 0.060 996 65 0.065 1004 70 0.070 1012 75 0.075 1020 80 0.080 1028 85 0.085 1036 90 0.090 1044 95 0.095 1052

100 0.100 1060 105 0.105 1068 110 0.110 1076 115 0.115 1084 120 0.120 1092 125 0.125 1100 130 0.130 1108 135 0.135 1116 140 0.140 1124 145 0.145 1132 150 0.150 1140 155 0.155 1148 160 0.160 1156 165 0.165 1164 170 0.170 1172 175 0.175 1180 180 0.180 1188 185 0.185 1196 190 0.190 1204 195 0.195 1212 200 0.200 1220 205 0.205 1228 210 0.210 1236 215 0.215 1244 220 0.220 1252 225 0.225 1260 230 0.230 1268 235 0.235 1276 240 0.240 1284 245 0.245 1292 250 0.250 1300 255 0.255 1308 260 0.260 1316 265 0.265 1324 270 0.270 1332 275 0.275 1340 280 0.280 1348 285 0.285 1356 290 0.290 1364 295 0.295 1372 300 0.300 1380

APPENDIX 1

69

Note: The chart shows light curtain Separation Distance (S) in relation to the systems response time (t1 + t2). In the chart 750mm has been chosen as a value for (H).

Page 72: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Angled Approach

To calculate separation distance (S) If B >30 degrees calculate S as for Normal approach If B <30 degrees calculate S as for Parallel approach

More detailed information on the application of safety light curtains is provided in the Health & Safety Executive booklet HSG180

APPENDIX 1 70

Page 73: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Mirrors Reflector mirrors can be provided enabling two or three sides of a machine to be safeguarded with, what is effectively a single light curtain. When mirrors are employed it is essential that the mounting of the transmitter unit, receiver unit and mirrors themselves are sufficiently rigid. Alignment becomes increasingly critical as the range and number of mirrors increase. Mirrors cause a reduction in optical efficiency, reducing the effective range. A guide to the practicality of using mirrors is given below.

Range of the light curtain

Maximum range through 1 mirror

Maximum range through 2 mirrors

0.5m - 5m 4m 3m 4m -10m 8m 6.5m

Total Light Path 1 Mirror 2 Mirror

2m# Easy Easy 4m* Easy Medium 6m* Medium Hard 8m* Hard Not Feasible

# Based upon a 012-105, * Based upon a 012-104

Note: Perimeter curtains will be easy to align, curtains over 900mm may be more difficult to align. Check with Smartcan technical department prior to ordering for a particular application. [email protected], Tel: +44 (0) 1536 401313, Fax : +44 (0) 1536 268354 Note: The angle of the light curtain striking the reflective surface must be within defined limits.

APPENDIX 2

71

Page 74: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Alignment though one mirror

1. Secure the transmitter, receiver and mirror units in the position in which they are intended to be used.

2. Ensure all units are perfectly upright in

all planes by using a sprit level. 3. If the units are floor mounted on stands ensure the floor is even.

Shim the floor mounts if necessary to ensure the units are all upright.

4. With one eye looking over the top of the receiver unit in line with

the centre of the extrusion look towards the reflective surface of the mirror, in a similar manner to looking through a gun sight.

5. A second person must adjust the mirror to the left and right until the

Perspex window of the transmitter unit can be seen reflected in the mirror.

6. If the light curtain is scanning over a long range it may be difficult

to see the reflection of the transmitter units Perspex window in the mirror. If so, cut a piece of white paper to the size of the Perspex window and mount directly in front of the window. Now repeat step 5.

7. If the reflection of the white paper is difficult to see in the mirror

then employ a third person to hold a flashlight in front of the transmitter unit with the light beam pointing directly in line with the Perspex window towards the mirror. Now repeat step 5.

8. Use shims to ensure the mirror is accurately aligned to enable

the infra red beams in the lightcurtain to reach the receiver. Alternatively, fabricate mirror mountings to include some form of adjustment to enable movement both left and right and also forward end backwards from the central axis of the mirror.

APPENDIX 2 72

Page 75: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

Alignment though two mirrors

9. Follow instruction 1-4 10. A second person must

adjust the position of the first mirror to the left and to the right until the entire length of the second mirror is reflected in the first mirror. If difficulties are experienced in seeing the reflection on the second mirror in the first mirror then use a piece of white paper cut to size and position in front of the second mirror.

11. If the reflection of the white paper is difficult to see in the first

mirror then employ a third person to hold a flashlight in front of the second mirror with the light beam pointing directly in line with its mirror housing towards the first mirror. Secure the first mirror.

12. Again follow instructions 1 to 4. 13. The second person must adjust the position of the second

mirror to the left and to the right until the entire length of the transmitter unit is reflected through both the first mirror and the second mirror. If difficulties are experienced in seeing the reflection of the transmitter unit through both the first then the second mirrors then use a piece of white paper cut to size and position in front of the transmitter unit.

14. If the reflection of the white paper is still difficult to see through

the first and second mirrors then employ a third person to hold a flashlight in front of the transmitter unit with the light beam pointing directly towards the second mirror. Secure the second mirror.

15. Ensure the mirrors are directly aligned thus enabling the infra

red beams of the transmitter to reach the receiver. Alternatively, fabricate mirror mountings to include some form

APPENDIX 2

73

Page 76: 1000 Plus Series Handbook - RS Components · HANDBOOK. 1000 PLUS SERIES . 1000 PLUS SERIES ... machine stop circuit and the installation is complete. There is NO interconnection cable

1000 PLUS SERIES

of adjustment to enable movement both left and right and also forwards and backwards from the central axis of each mirror.

16. Now turn on the power to the light curtain and check that the

green LED beam indicator, mounted on the receiver unit is ‘on’. If not, it may be necessary to finely adjust each mirror in turn to ensure the infa red energy from the transmitter unit is being reflected through the mirror(s) to the corresponding receiver unit.

Alignment of the light curtain using mirrors

With 1 Mirror

APPENDIX 2 74

Note: The mirror length must be a minimum of 100mm longer than the overall length of the light curtain to be installed eg. 50mm above and 50mm below either end of the light curtain