484

04. CHILLERS & HEAT PUMPS

Embed Size (px)

Citation preview

  • Products Guide 2015

  • The company

    Giordano Riello, founder and chairman of Aermec, assisted by his son

    Alessandro and daughter Raffaella, has solidly associated the Company

    name with precise values:

    Respect for the environment by using new eco-friendly refrigerants as

    well as innovative installations using water as the carrier fluid.

    Noise pollution control with low-noise emission products, which

    undergo scrupulous testing before being put on the market.

    Energy saving, the great challenge of the Third Millennium, with the

    development of combined heating and air conditioning systems where

    appliances are used only as and when necessary.

    Health care special filters trap the smallest particles in suspension and

    the Plasmacluster system cleans the air of dust mites and moulds, making

    for a cleaner, healthier environment and with the new germicidal lamps

    eliminating all virus and batteries.

  • Hystory

    1961 Giordano Riello sets up Riello Condizionatori, initially producing for

    contractors only. The story begins.

    1963 The Aermec brand is born and marks all future company products designed

    and manufactured on site.

    The brand name gains a stronghold as a major product name in Italy and

    throughout Europe.

    1970 Aermec can already supply fresh and warm air. Aermec presents the

    first dual section conditioner: the first split-system. Fancoil production

    starts.

    1980 The Eighties sees the development of water chillers and air handling units.

    1990 The Nineties mark the definitive consolidation of the company on the market.

    The Aermec brand is associated with advanced technology and high quality

    design.

    1998 The name makes the company. From 1 January Aermec becomes the

    company name as well as product brand.

    2000 The company consolidated its leadership in the production of fancoils, and

    laid the technological and production basis for strong growth in the field of

    high powered air-conditioning systems.

    2002 Design and technology: Aermec launched Omnia a new generation of

    fancoils, designed for domestic applications. OMNIA is the result of co

    operation with a worldwide prestigious designer.

    2004 The international market ask for number and Aermec answer. Giordano Riello

    make the producing system more technogical. High producing, quality and

    assistance: the success of Aermec is going to continue.

    2006 Aermec consolidated its presence in world markets with system appliances. A

    series of models to meet all design engineering requirements.

    2008 Aermec responds with more and more efficient units to the world challenge

    of energy saving with a special attention for our environment.

    2010 Aermec extends the use of inverter technology on its fancoils and chillers.

    The perfect integration of the new inverter technology with the most

    sophisticated control systems is best expressed in the VMF (Variable Multi

    Flow) Hydronic System - anew way to interpret comfort in the home and

    elsewhere.

    2011 Aermec turns 50. The company has developed and enlarged, always willing

    to understand and anticipate the needs of the market with innovative and

    quality products.

    Quality in innovation, in products, in pre-sales and after-sales services.

    Promotion of the philosophy of integrated design between designer and

    architect.

    Past success represents the commitment to the future.

  • 01. HYDRONIC TERMINALSFAN COILS

    A

    (m /h)C .C .

    (kW)H . C .

    (kW) PageFCX 110-1300 1-7,6 2,3-17 12FCXI Inverter 140-1140 1,5-8,6 2,9-17 16DUALJET 140-720 1,5-4,2 2,9-8,2 20Omnia HL 80-460 0,8-2,8 2,0-5,9 22Omnia UL 80-460 0,8-2,8 2,0-5,9 24Omnia Radiant 80-460 2-2,8 4,6-5,9 26

    With t a inet n ea ed ei ing in ta a n ith ta e eFCX_P 110-1300 1-7,6 2,29-17 30FCXI_P Inverter 140-1140 1,5-8,6 2,96-17 34Omnia UL_P 80-460 0,8-2,8 2,0-5,9 38

    With t a inet d t in ta a n ith high ta e eVED (030-340) 160-805 1,6-5,3 3,6-10,9 40VED (430-741) 750-2440 6,9-16 15,9-31,7 44VED_I (030-340) 160-805 1,6-5,3 3,6-10,9 48VED_I (430-741) 1060-2410 7,76-16 17,5-31,7 52

    Ca e e ei ing in ta a nVEC 130-613 1,32-4,28 56VEC_I 130-613 1,32-4,28 58FCL 260-1750 1,9-8,8 3,9-21,7 60FCLI Inverter 260-1750 1,9-8,8 3,9-21,7 64

    With a inet a in ta a nFCW 270-684 1,9-4,0 4,0-8,5 68

    With a inet eat ing ge mi ida amFHX 140-1140 1,5-6,9 2,9-15,1 70

    Fan i in ta a n nt and e i i n de i ePMZ 74Ven a a ma 76C nt ane 78VMF 80

    THERMOCONVECTORSCLIMAFON 0,9-2,5 84CLIMABOX 1,2-2,1 86

    02. HEAT RECOVERY UNITSREPURO 100-650 90TRS 150-1000 98UR 350-3300 100RPF 790-4250 102HRS 300-3920 106URX_CF 750-3300 110URHE_CF 1000-3300 114ERS 1000-5000 118ERSR 1100-16100 122

  • 03. AIR HANDLING UNITS

    AIR CONDITIONING UNITSAi ate

    (m /h)C .Ca .

    (kW)Heat. Ca .

    (kW) PageTUN 900-4000 4,7-26,4 11,2-51,1 128TS 930-4200 4,85-24,8 9,8-52,0 132TDA 800-3500 4,9-17,9 10,4-41,2 134TA 900-5000 4,7-31,8 14,2-78,3 136TN 3000-23000 15,6-96,4 25,2-178,5 140

    MODULAR AIR HANDLING UNITSNCS 907-51994 144NCD 1370-103550 146NCD_H 1800-30780 150SPL 025-130 2500-13000 152SPL 160-230 16000-25000 156ENERGY 4000-25000 160

    PAC AGED ROOF TOP UNITSRTX 09-16 51,6-129,9 50-127,5 164RTX 17-23 149-291 145-289 168RTY 01-10 30-134,8 29,1-142,2 172RTE 25-200 11,1-55,9 11,5-55,7 176RTE 240-400 82,5-152,1 77,5-148 180RTE 480-800 155,7-274,4 158,1-278,8 184

    04. CHILLERS & HEAT PUMPSAIR WATER CHILLERS AND REVERSIBLE HEAT PUMPSUnit ith m eIDROBLOC 3,5 3,8 190ANL 020-202 5,65-43,7 6,1-45,7 192ANL 290-650 55-133 196ANL 290H-650H 53-128 61-142 200ANLI 021H-101H 5,7-29,4 204ANK 020H-150H 6,7-29,2 7,8-33,5 208HBI 060-160 5,5-15,5 212SWP 2,1 216NRL 0280-0750 52,6-194 218NRL 0280H-0750H 50,6-178,9 58,4-205,3 222NRL 0800H-1800H 183-470 228-526 226NRB 0800-3600 217-1047 230NRB 0800H-3600H 196-969 210-1009 234NRK 0200-0700 33,5-148 42,3-175 238

    Unit ith m e and ent i ga P g FanMEC-W 11-55 242CL 025-200 5,82-41,3 7,85-43,8 244NRC 0275-1000 46-263 248NLC 0280-1250H 52-316 56,5-349 252

    Unit ith e m eNSM 1402-9603 302-2100 256NSH 1251-3602 235-670 276-789 264NSI 1251-5403 262-1249 272

    ne

    nene

    ne

  • 04. CHILLERS & HEAT PUMPS ( n n ed)AIR WATER CHILLERS AND REVERSIBLE HEAT PUMPS Ai ate

    (m /h)C .Ca .

    (kW)Heat. Ca .

    (kW) PageUnit ith ent i ga m eTBX 1401-4102 259-861 276

    Unit im tane and inde endent d n h t and d ate NRP 0200-0750 43-184 46-203 280NRP 0800-1800 199-475 242-547 284

    Chi e ith ee ingNRL 0280-0750FC 59-191 288NRL 0800-1800FC 196-452 292NRL 2000-3600FC 456-904 296NSM 1402-9603FC 306-2028 300NS 1251-7203FC HWT 243-1554 308NSM 1402-9603FC 306-2028 316NS 1251-7203FC HWT 243-1554 324NSI 1251-5403FC 257-1193 332

    WATER WATER CHILLERS AND REVERSIBLE HEAT PUMPSUnit ith m eVENICE 6,9-9,7 7,7-10,8 336WRL 026-161 6,5-43,6 338WRL 180-650 50-168 342WRL 026H-161H 6,2-40,2 7,8-47,9 346WRL 180H-650H 45-157 53-184 350NXW 0500-1400 105-384 119-434 354

    Unit ith e m eWSA 0601-2802 146-712 358WSB 0701-2802 171-701 362WSH 0701-2502 166-668 190-819 366WF 2512-6412 630-1549 370HWF 2512-6412 628-1524 374

    Unit ith ent i ga m eTW 110 284 378

    Unit im tane and inde endent d n h t and d ate NXP 0500-1650 109-501 123-560 380

    COMPONENTS FOR CHILLERS & HEAT PUMPSSAP 384WST 388TRA 392CSE-CDR-CVR-CGA-CMV 394WTE-WTR-WDR-WTS-WTA 406DMP 414

    ne

    ne

  • 05. PRECISION AIR CONDITIONERSDAS 06-60 6,4-64,7 418DAC 09-31 16-150 422DAC 06-35 6-200 426

    06. ROOM AIR CONDITIONERS

    MONOSPLITAi ate

    (m /h)C .Ca .

    (kW)Heat. Ca .

    (kW)Page

    SE 2,5-6,5 2,7-7 432SI 2,6-6,4 3-7 434HWI 2,6-6,4 2,7-6,4 436LCI 2,7-17,5 2,9-20 438DXE 20-39,5 22-42 442EWIH 0,9-8 0,9-9,5 444EFSI 0,9-4 0,9-6 443

    MULTISPLITMKM 2-13,6 2,5-14 448MIH 5,2-8,4 6,8-9 452

    VRF SYSTEMMDW 10-16 11-17,6 456MVF-MDS 10-60 11-63 460MVAS 12-28 14-30 464MVAM 22-180 22-200 468

    ASSOCIATED SOLUTIONSSMUFFO 472CWX 3,5-6,7 474FW-R 2,9-4 478

    ne

    ne

    ne

  • 12

    Fan coilsUniversal and floor installationFCX

    Fan coils for heating, cooling, and dehumidifying. FCX is designed to maintain in time the set temperature, ensuring very low sound levels. Installed in any type of plant 2/4 tubes and in combination with any of the heat generator even at low temperatures.Thanks to the availability of different versions, with front or lower air intake, with standard battery or increased, for hori-zontal or vertical installation, it is easy to choose the optimal solution for any need.

    - Vertical installation: FCX-A: vertical free-standing with switch FCX-AS: vertical free-standing without switch. Compatible

    with the VMF system FCX-ACT: vertical free standing with electronic thermostat FCX-APC: (FCX 22, 24, 32, 34, 36, 42, 44, 50, 54, 56, 62,

    64, 82, 84) vertical free-standing with electronic thermostat and Plasmacluster purifier

    FCX-B: front suction, without selector. Compatible with the VMF system

    - Vertical and horizontal installation: FCX-U: universal floor or wall/ceiling mounting.

    Adjustable air distribution grille, except for models 62, 64, 82, 84 and 102. Compatible with the VMF system

    FCX-UA: universal floor or wall/ceiling mounting. Grille with fixed fins. Compatible with the VMF system

    FCX-UE: universal floor or wall/ceiling mounting with direct expansion coil. Adjustable air distribution grille, except for models 62, 82 and 102.

    Versions standar coil (FCX 17, 22, 32, 36, 42, 50, 56, 62, 82 and 102)

    Versions increased coil (FCX 24, 34, 44, 54, 64, and 84) 3-speed ventilating unit Full compliance with the accident prevention standards

    Rounded line Automatic fan coil switch-off with closure of the air distri-

    bution grille Broad range of controls Metallic protective cabinet with rustproofing polyester

    paint Quiet operation Low loss of charge in the heat exchange batteries Electric motors with permanently inserted condensers Ease of installation and maintenance Air filter easy to remove and clean Extractable shrouds for easy, effective cleaning Water connections can be reversed during installation

    phase

    Features

    Aermecparticipate in the EUROVENT program: FCHthe products are present on the sitewww.eurovent-certification.com

    housing: RAL 9002head and feet: RAL 7044

    VERSION AVAILABLE SIZESFCX A 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102FCX AS 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102FCX ACT 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102FCX APC - 22 24 32 34 36 42 44 50 54 56 62 64 82 84 -

    FCX B 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102

    FCX U 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102FCX UA 17 22 24 32 34 36 42 44 50 54 56 - - - - -FCX UE - 22 - 32 - - 42 - 50 - - 62 - 82 - 102

    AMP: kit for the wall mounting installation of versions FCX U and UE.

    BC: Auxiliary condensate drip tray. Use the BC 5-6 tray accessory if horizontal, or BC 4 if vertical.

    BV: Single row hot water coil. Not available for 4-row versions or those with Plasmacluster.

    DSC4: Condensate drainage device for use when natural run-off is not possible.

    PC: Sheet metal panel to close rear of unit. RX: Armoured electric coil with safety thermo-

    stat. (Requires a thermostat with heater manage-ment). Not available for 4-row versions or those with Plasmacluster.

    SE: Manually operated fresh air intake louver. SIT 3 - 5: Thermostat Interface Cards. They allow

    the creation of a network of fan coils (max. 10) commanded by a central control panel (selector or thermostat).

    SIT3: commands the 3 fan speeds and must be installed on each fan coil of the network; receives the commands from the selector or the

    SIT5 card. SIT5: commands the 3 fan speeds and up to 2

    valves (four pipes systems); sends the commands of the thermostat to the fan coils network.

    SW3: water temperature probe that gives the auto-matic season change feature to electronic thermo-stats supplied with water-side change over.

    SWA: SWA external probe accessory (length L = 6m). The probe detects the temperature of the ambient air if connected to the connector (A) of the panel FMT21; the ambient air temperature probe incorporated in the panel is automatically deactivated. Detects the temperature of the water in the system, for ventilation consent, if connected to the connector (W) of the FMT21 panel. Two SWA probes can be connected to the panel FMT21 simultaneously.

    VCF: the kit contains a motorised 3-way valve with insulating shell, plus coupling and pipes in insulated copper. For 3/4-row and 1-row coils (BV). Combine the SW3 probe with FCX ACT, too. Versions with

    230V and 24V~50Hz power supply. VCFD: Kit consisting of powered 2-way valve,

    copper couplings and pipes. For 3/4-row and 1-row coils (BV). Combine the SW3 probe with FCX ACT, too. Versions with 230V and 24V~50Hz power supply.

    VCF_X4: The valve kits are designed for fan coil units with single coil, installed in a 4 pipe sys-tem with the "Cooling" and "Heating" circuits totally separated. The kit consists of 2 valves of 3-way 4 port connection complete with electro-thermal actuators, insulating shells for the valves and associated hydraulic piping. VCF1X4L Valve kit for left hand connection fan coil units. VCF1X4R Valve kit for right hand connection fan coil units. Power supply: 230V ~ 50Hz.

    ZX: Feet for floor-standing installations for A-AS-ACT-APC models.

    Control panels(1) and VMF System(2): the charac-teristics are described on the appropriate card.

    Accessories

    FCX_A

    FCX-UZX

  • 13

    Accessories Size Versions17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102

    FMT10 FMT21 (1) AS-B-U-UAKTLM (1) AS-B-U-UAPTI (1) AS-B-UA-U(62 - 102)PX PX2 PX2C6 (1) (3) AS-B-U-UAPXBI PXAI (1) AS-B-U-UAPXAE (1) AS-B-U-UAPXAR (1) AS-B-U-UATF1 (1) AS-B-U-UATPF (1) AS-B-U-UAWMT05 WMT06 WMT10 (1) AS-B-U-UAVMF-E4 VMF-E4D (2) AS-B-U-UAVMF-E2 (2) AS-B-UA-U(62 - 102)VMF-E0 VMF-E1 (2) AS-B-U-UAAMP U-UA-UEAMP20 U-UA-UE

    BC4 A-AS-ACT-APC-B-U-UA-UE5 U-UA-UE6 U-UA-UE

    BV

    117 (4) A-AS-B-U-UA-UE122 (4) A-AS-B-U-UA-UE132 (4) A-AS-B-U-UA-UE142 (4) A-AS-B-U-UA-UE162 (4) A-AS-B-U-UA-UE

    DSC4 (5)(6) A-AS-ACT-APC-B-U-UA-UE

    PC

    17 A-AS-ACT-APC-B-UA18 U-UE22 A-AS-ACT-APC-B-UA23 U-UE32 A-AS-ACT-APC-B-UA33 U-UE42 A-AS-ACT-APC-B-UA43 U-UE62 A-AS-ACT-B-U-UA-UE

    RX

    17 (4) AS-B-U-UA22 (4) AS-B-U-UA-UE32 (4) AS-B-U-UA-UE42 (4) AS-B-U-UA-UE52 (4) AS-B-U-UA-UE62 (4) AS-B-U-UA-UE

    SE

    15X A-AS-ACT-APC20X A-AS-ACT-APC30X A-AS-ACT-APC40X A-AS-ACT-APC80X A-AS-ACT-APC

    SIT3 AS-B-U-UA-UE5 AS-B-U-UA-UE

    SW3 AS-B-U-UASWA AS-B-U-UA

    VCF

    1X4L - 1X4R (7) AS-B-U-UA2X4L - 2X4R (7) AS-B-U-UA3X4L - 3X4R (7) AS-B-U-UA41-4124 (7)(8) AS-ACT-APC-B-U-UA42-4224 (7)(8) AS-ACT-APC-B-U-UA43-4324 (7)(8) AS-ACT-APC-B-U-UA44-4424 (7)(8)(9) AS-B-U-UA45-4524 (7)(8)(9) AS-B-U-UA

    VCFD

    1-124 (7)(8) AS-ACT-APC-B-U-UA2-224 (7)(8) AS-ACT-APC-B-U-UA3-324 (7)(8) AS-ACT-APC-B-U-UA4-424 (7)(8)(9) AS-B-U-UA

    ZX5 A-AS-ACT-APC6 A-AS-ACT-APC

    (1)(2) The characteristics are described on the appropriate card.(3) PX2C6, PX2 panel in multiple 6-piece pack.(4) Accessoires is not available in the model with Plasmacluster filter(5) The DSC4 accessory is not compatible with AMP and BC4_5_6 accessories(6) DSC4 and accessoires VMF-system tray cannot be installed together on a single fan coil.(7) The VCF/VCFD valve and the BC4 tray cannot be installed together on a single fan coil.(8) = VCF4124-4224-4324-4424-4524 / VCFD124-224-324-424 they are 24V(9) Only for the BV 1-row coil accessory.

  • 14

    Technical data

    Mod. FCX Vel. 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102HEATING PERFORMANCE (2 PIPE CONFIGURATION)

    Heating capacity (70C)(1) W H 2296 2960 3912 5354 5964 6413 6618 8600 8191 10100 9648 12919 14300 15140 17100 17019 (1) W M 2033 2531 3103 4065 4801 4983 5521 6930 7529 8759 8434 10942 11501 13349 14421 15242 (1) W L 1686 1906 2097 3165 3728 4188 4062 5200 5021 6241 6056 8327 8499 10771 11198 12558

    Water flow rate(1) l/h H 201 260 343 470 523 563 581 754 718 886 846 1133 1254 1328 1500 1493 (1) l/h M 178 222 272 357 421 437 484 608 660 768 740 960 1009 1171 1295 1337 (1) l/h L 148 167 184 278 327 367 356 456 440 547 531 730 745 945 982 1101

    Pressure drop(1) kPa H 3 6 4 20 11 13 15 22 15 23 42 17 23 21 32 43 (1) kPa M 2 4 3 12 7 10 11 15 13 18 33 12 16 16 23 34 (1) kPa L 1 3 1 8 5 8 6 9 6 9 19 7 9 11 15 24

    Heating capacity (50C)(2) W H 1360 1770 2320 3160 3550 3800 3960 4950 4870 6100 5380 7500 8400 7960 10200 10000 (2) W M 1200 1510 1840 2400 2860 2950 3300 4140 4480 5220 4840 6430 6800 6860 8600 9000 (2) W L 990 1130 1250 2060 2220 2480 2430 3170 3000 3700 3680 4880 5040 5200 6700 7440

    Water flow rate(2) l/h H 172 258 298 413 482 482 585 765 721 855 791 836 1092 1189 1479 1311 (2) l/h M 144 210 236 316 392 370 478 617 604 743 662 752 896 860 1259 1183 (2) l/h L 112 144 174 267 303 311 397 463 432 533 475 554 674 738 992 979

    Pressure drop(2) kPa H 2 6 3 16 9 9 15 23 15 22 22 9 18 21 31 33 (2) kPa M 2 5 2 10 7 7 13 15 11 17 20 7 13 12 23 27 (2) kPa L 1 2 1 7 4 6 8 9 6 9 15 4 8 9 15 19

    HEATING PERFORMANCE (4 PIPE CONFIGURATION - with additional heat exchanger)

    Heating capacity (70C)(3) W H 1400 1770 - 2850 - - 3460 - 4380 - - 5490 - 6410 - 6810(3) W M 1200 1510 - 2450 - - 3410 - 3940 - - 4700 - 6300 - 6230(3) W L 990 1130 - 2030 - - 2660 - 3220 - - 3870 - 5300 - 5430

    Water flow rate(3) l/h H 123 155 - 250 - - 303 - 384 - - 482 - 562 - 597(3) l/h M 105 132 - 215 - - 299 - 346 - - 412 - 553 - 547(3) l/h L 87 99 - 178 - - 233 - 282 - - 339 - 465 - 476

    Pressure drop(3) kPa H 3 6 - 16 - - 21 - 35 - - 16 - 15 - 19(3) kPa M 2 5 - 12 - - 20 - 30 - - 12 - 14 - 16(3) kPa L 2 3 - 8 - - 14 - 21 - - 10 - 11 - 13

    COOLING PERFORMANCE (2 and 4 PIPE CONFIGURATIONS)

    Total cooling capacity(4) W H 1000 1500 1730 2400 2800 2800 3400 4450 4190 4970 4600 4860 6350 6910 8600 7620(4) W M 840 1220 1370 1840 2280 2150 2780 3590 3510 4320 3850 4370 5210 5000 7320 6880(4) W L 650 840 1010 1550 1760 1810 2310 2690 2510 3100 2760 3220 3920 4290 5770 5690

    Sensible cooling capacity(4) W H 830 1240 1380 1900 2130 2200 2760 3300 3000 3540 3500 3980 5030 5680 5780 5530(4) W M 690 1000 1090 1570 1720 1820 2110 2640 2540 3060 3070 3300 4100 3780 4870 5350(4) W L 510 670 760 1110 1250 1280 1630 1960 1790 2170 2120 2440 3060 2970 2800 4420

    Water flow rate (4) l/h H 172 258 298 413 482 482 585 765 721 855 791 836 1092 1189 1479 1311(4) l/h M 144 210 236 316 392 370 478 617 604 743 662 752 896 860 1259 1183(4) l/h L 112 144 174 267 303 311 397 463 432 533 475 554 674 738 992 979

    Pressure drop(4) kPa H 3 6 3 28 14 28 14 40 19 26 38 17 13 22 30 37(4) kPa M 2 5 2 17 10 17 10 27 14 21 28 14 9 12 22 31(4) kPa L 1 3 1 13 6 13 7 16 8 12 15 8 6 9 15 22

    Air flow ratem3/h H 200 290 290 450 450 450 600 600 720 720 720 920 920 1140 1140 1300m3/h M 160 220 220 350 350 350 460 460 600 600 600 720 720 930 930 1120m3/h L 110 140 140 260 260 260 330 330 400 400 400 520 520 700 700 900

    Fanstype centrifugaln 1 1 1 2 2 2 2 2 2 2 2 3 3 3 3 3

    Absorbed powerW H 35 25 33 44 44 44 57 57 67 76 76 82 91 106 106 131W M 29 22 29 33 34 33 43 43 46 52 52 61 60 80 80 100W L 19 19 25 25 28 25 30 30 34 38 38 40 38 59 59 80

    Max. input current (A) 0,16 0,12 0,25 0,21 0,45 0,21 0,28 0,51 0,35 0,36 0,35 0,40 0,48 0,49 0,62 0,58

    Sound power level(5) dB(A) H 45 50 51 48 48 48 51 55 56 56 56 57 57 61 61 66(5) dB(A) M 38 43 46 41 41 41 44 50 51 53 51 51 51 56 57 61(5) dB(A) L 31 31 35 34 36 34 37 41 42 44 42 42 44 51 51 56

    Sound pressure level(6) dB(A) H 37 42 43 40 40 40 43 47 48 48 48 49 49 53 53 58(6) dB(A) M 30 35 38 33 33 33 36 42 43 45 43 43 43 48 49 53(6) dB(A) L 23 23 27 26 28 26 29 33 34 36 34 34 36 43 43 48

    Water content l 0,6 0,8 1,0 1,1 1,5 1,5 1,5 1,9 1,5 1,9 1,9 2,5 3,4 2,5 3,4 2,5

    Coil connections (4R) - - 3/4" - 3/4" - - 3/4" - 3/4" - - 3/4" - 3/4" - (3R) 1/2" 1/2" - 1/2" - 3/4" 3/4" - 3/4" - 3/4" 3/4" - 3/4" - 3/4" (1R) 1/2" 1/2" - 1/2" - 1/2" 1/2" - 1/2" - 1/2" 1/2" - 1/2" - 1/2"

    Speed connectedH V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3M V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2L V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1

    Power supply 230V/1/50Hz

    H max. speed; M med. speed; L min. speedHeating mode2 pipes system configuration(1) Room air temperature 20C b.s.; Inlet water temperare 70C; T water 10C2 pipes system configuration (EUROVENT)(2) Room air temperature 20C b.s.; Inlet water temperare 50C; Water flow rate as in cooling mode4 pipes system configuration (with additional heat exchanger) (EUROVENT)(3)Room air temperature 20C b.s.; Inlet water temperare 70C; T water 10CCooling mode (EUROVENT)(4) Room air temperature 27C b.s./19C b.u.; Inlet water temperare 7C; T water 5C(5) Sound power level on the basis of measurements made in compliance with Eurovent 8/2(6) Sound pressure level (A-weighted) measured in the room with volume V=85m3, reverberation time t = 0.5 s; Direction factor Q = 2; Distance r = 2.5mNote: For more information, please refer to the program selection and the technical documentation available on the website www.aermec.com

  • Aermec S.p.A.Via Roma, 996 - 37040 Bevilacqua (VR) - ItalyTelephone 0442633111 - Telefax 044293577www.aermec.com

    15Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data.

    Cod

    .: SF

    CX

    UY.

    19 /

    1501

    A

    B C

    A

    BC

    B

    A

    C

    D

    Dimensions and Weight

    Mod FCX (A - AS - ACT - APC) 17 22 / 24 32/34/36 42/44 50/54/56 62/64 82/84 102Height with feet A mm 563 563 563 563 563 688 688 688Width B mm 640 750 980 1200 1200 1320 1320 1320depth C mm 220 220 220 220 220 220 220 220Feet height D mm 105 105 105 105 105 125 125 125Weight (without feet) kg 13 15 20 24 24 34 34 34

    Mod FCX (U - UE) 17 22 / 24 32/34/36 42/44 50/54/56 62/64 82/84 102Height A mm 520 520 520 520 520 590 590 590Width B mm 640 750 980 1200 1200 1320 1320 1320depth C mm 220 220 220 220 220 220 220 220Weight kg 13 15 20 24 24 34 34 34

    Mod FCX (UA) 17 22 / 24 32/34/36 42/44 50/54/56Height A mm 490 490 490 490 490Width B mm 640 750 980 1200 1200depth C mm 220 220 220 220 220Weight kg 13 15 20 24 24

    Mod FCX (B) 17 22 / 24 32/34/36 42/44 50/54/56 62 / 64 82 / 84 102Height A mm 490 490 490 490 490 590 590 590Width B mm 640 750 980 1200 1200 1320 1320 1320depth C mm 220 220 220 220 220 220 220 220Weight kg 13 15 20 24 24 34 34 34

    (standard and increased coil)FCX_AFCX_ASFCX_ACTFCX_APC

    ZX accessoires

    FCX_U 17-22-32-36-42-50-56 (standard coil)FCX_U 24-34-44-54 (increased coil)FCX_UE 22-32-42-50 (standard coil)

    FCX_BFCX_UA 17-22-32-36-42-50-56 (standard coil)FCX_UA 24-34-44-54 (increased coil)FCX_U 62-82-102 (standard coil)FCX_U 64-84 (increased coil)FCX_U 62-82-102 (standard coil)

  • 16

    Fan coils with Brushless Inverter motor (EC)Universal and floor installationFCXI

    Fan coils with with inverter technology, for heat-ing, cooling and dehumidifying, specific to work in sensible environment.Equipped with inverter Brushless motor for an high effciency and a continuos air flow rate modulation in order to increased comfort and guarantee electric saving. The inverter motor allows a better air temperature regulation on based on the real indoor envirorement require-ments without temperature swinging.. The FCXI are the ideal solution for 2/4-pipe systems and for tertiary and commercial installations.Thanks to the availability of different versions, with front or lower air intake, with standard battery or increased, for horizontal or vertical installation, it is easy to choose the optimal solution for any need.

    Versions:FCXI AS: with tall cabinetFCXI U: with universal cabinet for floor/ ceiling installationFCXI ACT: vertical free standing with electronic ther-mostat Fan unit with Brushless motor (continuous 0-100%

    speed variation) Full compliance with the accident prevention

    standards Rounded line Metallic protective cabinet with rustproofing poly-

    ester paint Adjustable air distribution grille, for U versions Fan coil automatic power-off function with closure

    of the air delivery grille, for U versions Quiet operation

    Low loss of charge in the heat exchange batteries Ease of installation and maintenance Air filter easy to remove and clean Extractable shrouds for easy, effective cleaning Water connections can be reversed during installa-

    tion phase

    Characteristics

    ENERGY SAVINGS OF 50% COMPARED WITH A FAN COIL WITH TRADITIONAL 3-SPEED MOTOR

    VERY QUIET OPERATION TOTAL COMFORT: REDUCED TEMPERATURE AND HUMIDITY VARIATIONS IN THE AIR-CONDITIONED ROOMS

    Accessories

    FCXI U

    FCXI A

    housing: RAL 9002

    head and feet: RAL 7044

    Aermecparticipate in the EUROVENTprogram: FCHthe products are present on the sitewww.eurovent-certification.com

    WMT21: Control panel with electronic thermostat and LCD monitor. Wall mounting.

    PTI2: Control panel with electronic thermostat on the fan coil installation.

    VMF System: the characteristics are described on the appropriate card.

    AMP: Kit for ceiling installation, for versions FCXI U. BC: Auxiliary condensate drip tray. BV: 1-row hot water coil. The accessory is not available for the 4R models. DSC4: Condensate drainage device for use when

    natural run-off is not possible. MA: A-type covering cabinet (use tray accessory

    BC 4 for FCXI AS, ACT).

    MU: U-type covering cabinet (use tray accessory BC 5-6 for FCXI U).

    PC: Sheet metal panel to close rear of unit. SE: External air damper with command, FCXI AS

    and ACT. SWAI: Water temperature probe for WMT21 con-

    trol panels. Cable length L = 2m. VMF-SW1: Additional water sensor may be used

    for 4-pipe system with VMF-E1 and E18 thermo-stats for the maximum control in the cold range

    VCF: Kit comprising motorized 3 way valve with isolating shell, unions and insulated copper pipes. For 3/4-row and 1-row coils (BV). Versions with 230V and 24V~50Hz power supply.

    VCFD: Kit consisting of powered 2-way valve,

    copper couplings and pipes. For 3/4-row and 1-row coils (BV).

    VCF_X4: The valve kits are designed for fan coil units with single coil, installed in a 4 pipe system with the "Cooling" and "Heating" circuits totally separated. The kit consists of 2 valves of 3-way 4 port connection complete with electro-thermal actuators, insulating shells for the valves and asso-ciated hydraulic piping. VCF1X4L Valve kit for left hand connection fan coil units. VCF1X4R Valve kit for right hand connection fan coil units. Power supply: 230V ~ 50Hz.

    ZX: Feet for floor installations for FCXI AS and ACT models.

  • 17

    Accessories

    (1)The DSC4 is not compatible with BC4_5_6_8_9 AMP and accessories. The DSC4 accessory is compatible with AMP20 accessory. (2) The DSC4 and the VMF-system can not be installed simultaneously on the same fancoil(3) The BC4 accessory is not available for models fitted with VCF / VCFD valve.(4) VCF4124-4224-4324-4424-4524 / VCFD124-224-324-424 are 24V(5) Only for accessory coil BV 1R.

    FCXI20 24 30 34 36 40 44 50 54 56 80 84

    WMT21 AS - USWAI AS - UVMF-SW1 AS - UPTI2 AS - e 80U-84UVMF-E18 AS - UVMF-E2 AS - UVMF-E2D UVMF-E4 / E4D AS - UVMF-E5N / B AS - UAMP U AMP20 U

    BC4 AS - ACT5 U 6 U

    BV

    122 AS - U - ACT132 AS - U - ACT142 AS - U - ACT162 AS - U - ACT

    DSC4 (1)(2) AS - U - ACT

    PC

    22 AS - ACT23 U32 AS - ACT33 U42 AS - ACT43 U62 AS - U - ACT

    SE

    20X AS - ACT30X AS - ACT40X AS - ACT80X AS - ACT

    VCF

    1X4L o R (3) AS - U - ACT2X4L o R (3) AS - U - ACT3X4L o R (3) AS - U - ACT41 - 4124 (3)(4) AS - U - ACT42 - 4224 (3)(4) AS - U - ACT43 - 4324 (3)(4) AS - U - ACT44 - 4424 (3)(4)(5) AS - U - ACT45 - 4524 (3)(4) AS - U - ACT

    VCFD

    1 - 124 (3) AS - U - ACT2 - 224 (3) AS - U - ACT3 - 324 (3) AS - U - ACT4 - 424 (3)(5) AS - U - ACT

    ZX5 AS - ACT6 AS - ACT

  • 18

    Technical data

    Mod. FCXI Vel. 20 24 30 34 36 40 44 50 54 56 80 84HEATING PERFORMANCE (2 PIPE CONFIGURATION)

    Heating capacity (70C)(1) W H 2960 3912 5354 5964 6413 6618 8600 8191 10100 9648 15140 17100(1) W M 2531 3103 4065 4801 4983 5521 6930 7529 8759 8434 13349 14421(1) W L 1906 2097 3165 3728 4188 4062 5200 5021 6241 6056 10771 11198

    Water flow rate(1) l/h H 260 343 470 523 563 581 754 718 886 846 1328 1500(1) l/h M 222 272 357 421 437 484 608 660 768 740 1171 1295(1) l/h L 167 184 278 327 367 356 456 440 547 531 945 982

    Pressure drop(1) kPa H 6 4 20 11 13 15 22 15 23 42 21 32(1) kPa M 4 3 12 7 10 11 15 13 18 33 16 23(1) kPa L 3 1 8 5 8 6 9 6 9 19 11 15

    Heating capacity (50C)(2) W H 1.770 2.320 3.160 3.550 3.800 3.960 4.950 4.870 6.100 5.380 7.960 10.200(2) W M 1.510 1.840 2.400 2.860 2.950 3.300 4.140 4.480 5.220 4.840 6.860 8.600(2) W L 1.130 1.250 2.060 2.220 2.480 2.430 3.170 3.000 3.700 3.680 5.200 6.700

    Water flow rate(2) l/h H 258 298 413 482 482 585 765 721 855 791 1189 1479(2) l/h M 210 236 316 392 370 478 617 604 743 662 860 1259(2) l/h L 144 174 267 303 311 397 463 432 533 475 738 992

    Pressure drop(2) kPa H 6 3 16 9 9 15 23 15 22 22 21 31(2) kPa M 5 2 10 7 7 13 15 11 17 20 12 23(2) kPa L 2 1 7 4 6 8 9 6 9 15 9 15

    HEATING PERFORMANCE (4 PIPE CONFIGURATION - with additional heat exchanger)

    Heating capacity (70C)(3) W H 1.770 - 2.850 - 2.850 3.460 - 4.380 - 4.380 6.410 -(3) W M 1.510 - 2.450 - 2.450 3.410 - 3.940 - 3.940 6.300 -(3) W L 1.130 - 2.030 - 2.030 2.660 - 3.220 - 3.220 5.300 -

    Water flow rate(3) l/h H 155 - 250 - 250 303 - 384 - 384 562 -(3) l/h M 132 - 215 - 215 299 - 346 - 346 553 -(3) l/h L 99 - 178 - 178 233 - 282 - 282 465 -

    Pressure drop(3) kPa H 6 - 16 - 16 21 - 35 - 35 15 -(3) kPa M 5 - 12 - 12 20 - 30 - 30 14 -(3) kPa L 3 - 8 - 8 14 - 21 - 21 11 -

    COOLING PERFORMANCE (2 and 4 PIPE CONFIGURATIONS)

    Total cooling capacity(4) W H 1500 1730 2400 2800 2800 3400 4450 4190 4970 4600 6910 8600(4) W M 1.220 1.370 1.840 2.280 2.150 2.780 3.590 3.510 4.320 3.850 5.000 7.320(4) W L 840 1010 1550 1760 1810 2310 2690 2510 3100 2760 4290 5770

    Sensible cooling capacity(4) W H 1240 1380 1900 2130 2200 2760 3300 3000 3540 3500 5680 5780(4) W M 1.000 1.090 1.570 1.720 1.820 2.110 2.640 2.540 3.060 3.070 3.780 4.870(4) W L 670 760 1110 1250 1280 1630 1960 1790 2170 2120 2970 2800

    Water flow rate (4) l/h H 258 298 413 482 482 585 765 721 855 791 1189 1479(4) l/h M 210 236 316 392 370 478 617 604 743 662 860 1259(4) l/h L 144 174 267 303 311 397 463 432 533 475 738 992

    Pressure drop(4) kPa H 5,8 3 28 13,8 28 14,3 40,2 19,3 25,9 38 22 29,5(4) kPa M 5 2 17 10 17 10 27 14 21 28 12 22(4) kPa L 2,5 1 13 6 12,7 7 16,3 7,6 11,7 15,1 9,3 14,7

    Air flow ratem3/h H 290 290 450 450 450 600 600 720 720 720 1140 1140m3/h M 220 220 350 350 350 460 460 600 600 600 930 930m3/h L 140 140 260 260 260 330 330 400 400 400 700 700

    Fanstype centrifugaln 1 1 2 2 2 2 2 2 2 2 3 3

    Absorbed powerW H 12 12 13 13 13 17 17 37 37 37 80 80W M 8 8 7 7 7 9 9 20 20 20 40 40W L 5 5 4 4 4 6 6 8 8 8 30 30

    Max. input current (A) 0,12 0,12 0,21 0,21 0,21 0,28 0,28 0,35 0,35 0,35 0,49 0,49

    Sound power level(5) dB(A) H 50 51 48 48 48 51 55 56 56 56 61 61(5) dB(A) M 43 46 41 41 41 44 50 51 53 51 56 57(5) dB(A) L 31 35 34 36 34 37 41 42 44 42 51 51

    Sound pressure level(6) dB(A) H 42 43 40 40 40 43 47 48 48 48 53 53(6) dB(A) M 35 38 33 33 33 36 42 43 45 43 48 49(6) dB(A) L 23 27 26 28 26 29 33 34 36 34 43 43

    H max. speed; M med. speed; L min. speedHeating performance2 pipes system configuration(1) Room air temperature 20C b.s.; Inlet water temperare 70C; T water 10C2 pipes system configuration (EUROVENT)(2) Room air temperature 20C b.s.; Inlet water temperare 50C; Water flow rate as in cooling mode4 pipes system configuration (with additional heat exchanger) (EUROVENT)(3)Room air temperature 20C b.s.; Inlet water temperare 70C; T water 10CCooling performance (EUROVENT)(4) Room air temperature 27C b.s./19C b.u.; Inlet water temperare 7C; T water 5C(5) Sound power level on the basis of measurements made in compliance with Eurovent 8/2(6) Sound pressure level (A-weighted) measured in the room with volume V=85m3, reverberation time t = 0.5 s; Direction factor Q = 2; Distance r = 2.5mNote: For more information, please refer to the program selection and the technical documentation available on the website www.aermec.com

  • Aermec S.p.A.Via Roma, 996 - 37040 Bevilacqua (VR) - ItalyTel. +39 04 42 63 31 11 - Telefax +39 044 29 3577www.aermec.com

    19Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data.

    Technical data

    Cod

    .: SF

    CX

    IUY.

    06 /

    1502

    Dimensions (mm)

    Mod. FCXI Vel. 20 24 30 34 36 40 44 50 54 56 80 84Water content l 1 1,11 1,5 1,5 1,48 1,9 1,48 1,9 1,9 2,52 3,4 2,52

    Coil connections (4R) - 3/4" - 3/4" - - 3/4" - 3/4" - - 3/4" (3R) 1/2" - 1/2" - 3/4" 3/4" - 3/4" - 3/4" 3/4" - (1R) 1/2" - 1/2" - 1/2" 1/2" - 1/2" - 1/2" 1/2" -

    Work percentage compared to the configuration signal

    % H 90 90 90 90 90 90 90 90 90 90 90 90% M 84 84 84 84 84 82 82 86 86 86 84 84% L 44 44 48 48 48 52 52 60 60 60 45 45

    Power supply 230V/1/50Hz

    A

    B C

    A

    BC

    B

    A

    C

    D

    Mod FCXI (AS - ACT) 20 / 24 30 / 34 / 36 40 / 44 50 / 54 / 56 80 / 84Height with feet A mm 563 563 563 563 688Width B mm 750 980 1200 1200 1320Depth C mm 220 220 220 220 220Height of feet D mm 105 105 105 105 125Weight (without feet) kg 15 20 24 24 34

    Mod FCXI (U) 20 / 24 30 / 34 / 36 40 / 44 50 / 54 / 56 80 / 84Height A mm 520 520 520 520 590Width B mm 750 980 1200 1200 1320Depth C mm 220 220 220 220 220Weight kg 15 20 24 24 34

    (standard coil and augmented)FCXI_ASFCXI_ACTFCXI_U

    ZX (accessoires)

    FCXI_U 20-30-36-40-50-56 (standard coil)FCXI_U 24-34-44-54 (augmented coil)

    FCXI_U 80 (standard coil)FCXI_U 84 (augmented coil)

  • 20

    Controlled outlet fan coilsFloor installationDUALJET

    Controlled outlet fan coils available in 4 sizes:

    - Vertical installation: DUALJET: without control panel but with VMF-

    E0 thermostat, ready for installation on the network as a Slave unit or as a single or Master unit if combined with the wired panel accessories VMF-E4 / VMF-E4D or VMF-E2D control panel.

    All units are compatible with the VMF system When installing a centralized control VMF-E5B / VMF-E5N or BMS third party will need to contact your

    Switching the front air outlet or from the top, using the selector on the unit.

    Front outlet for heating operation. Outlet from the top for cooling operation. Versions with 3-row coil (sizes 20, 30, 40, 50) 3-speed ventilating unit Full compliance with the accident prevention

    standards Rounded line Metallic protective cabinet with rustproofing

    polyester paint

    Plastic feet available as accessory Quiet operation Low loss of charge in the heat exchange

    batteries Electric motors with permanently inserted

    condensers Ease of installation and maintenance Air filter easy to remove and clean Extractable shrouds for easy, effective cleaning Water connections can be reversed during

    installation phase

    Features

    DUALJET: comfort, everywhereThe perception of uneven temperature distribution, especially vertically, is one of the main factors that can drastically reduce occupants' perceived well-being.

    The innovative DUALJET fan coil makes the room more comfortable, by directing the air in such a way as to provide uniform temperature distribution throughout the room.

    In winter, warm air is directed towards the floor; in the summer, cool air is directed towards the ceiling.

    Control panel and VMF System: The features are described in the dedicated cards.

    * VMF-E1D Please contact us. ZX: Feet for floor mounting VCF: the kit contains a motorised 3-way valve

    with insulating shell, plus coupling and pipes in insulated copper. For 4-row, 3-row and 1-row coils (BV). Versions with 230V and 24V~50Hz power supply.

    VCFD: Kit consisting of powered 2-way valve, copper couplings and pipes. For 4-row, 3-row and 1-row coils (BV). Versions with 230V and 24V~50Hz power supply.

    VCF_X4: The valve kits are designed for fan coil units with single coil, installed in a 4 pipe sys-tem with the "Cooling" and "Heating" circuits totally separated. The kit consists of 2 valves of 3-way 4 port connection complete with electro-

    thermal actuators, insulating shells for the valves and associated hydraulic piping. VCF1X4L Valve kit for left hand connection fan coil units. VCF1X4R Valve kit for right hand connection fan coil units. Power supply: 230V ~ 50Hz.

    Accessories

    Aermecparticipate in the EUROVENTprogram: FCHthe products are present on the sitewww.eurovent-certification.com

    Whitehousing RAL 9002head and feet RAL 7044

    DUALJET 20 30 40 50VMF-E4 VMF-E4D VMF-E2D ZX5 VCF41 VCF4124 VCF42 VCF4224 VCFD1 VCFD124 VCFD2 VCFD224 VCF1X4L VCF1X4R VCF2X4L VCF2X4R

  • Aermec S.p.A.Via Roma, 996 - 37040 Bevilacqua (VR) - ItalyTel. 0442633111 - Telefax 044293577www.aermec.com

    21Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data.

    Technical data

    Cod

    e: S

    DJU

    Y.04

    / 150

    1

    (1) Unit in standard configuration without accessories

    Mod. DUALJET Vel. 20 30 40 50HEATING PERFORMANCE (2 PIPE CONFIGURATION)

    Heating capacity (70C)(1) W H 2960 5354 9918 8191(1) W M 2531 4065 5521 7529(1) W L 1906 3165 4062 5021

    Water flow rate(1) l/h H 260 470 581 718(1) l/h M 222 357 484 660(1) l/h L 167 278 356 440

    Pressure drop(1) kPa H 6 20 15 15(1) kPa M 4 12 11 13(1) kPa L 3 8 6 6

    Heating capacity (50C)(2) W H 1770 3160 3960 4870(2) W M 1510 2400 3300 4480(2) W L 1130 2060 2430 3000

    Water flow rate(2) l/h H 258 413 585 721(2) l/h M 210 316 478 604(2) l/h L 144 267 397 432

    Pressure drop(2) kPa H 6 16 15 15(2) kPa M 5 10 13 11(2) kPa L 2 7 8 6

    cooling PERFORMANCE

    Total cooling capacity(3) W H 1500 2400 3400 4190(3) W M 1220 1840 2780 3510(3) W L 840 1550 2310 2510

    Sensible cooling capacity(3) W H 1240 1900 2760 3000(3) W M 1000 1570 2110 2540(3) W L 670 1110 1630 1790

    Water flow rate (3) l/h H 258 413 585 721(3) l/h M 210 316 478 604(3) l/h L 144 267 397 432

    Pressure drop(3) kPa H 5,8 28 14,3 19,3(3) kPa M 5 17 10 14(3) kPa L 2,5 13 7 7,6

    Air flow ratem3/h H 290 450 600 720m3/h M 220 350 460 600m3/h L 140 260 330 400

    Fanstype Centrifugaln 1 2 2 2

    Absorbed powerW H 25 44 57 67W M 22 33 43 46W L 19 25 30 34

    Max. input current A 0,12 0,21 0,28 0,35

    Sound power level(4) dB(A) H 50 48 51 56(4) dB(A) M 43 41 44 51(4) dB(A) L 31 34 37 42

    Sound pressure level(5) dB(A) H 42 40 43 48(5) dB(A) M 35 33 36 43(5) dB(A) L 23 26 29 34

    Water content l 0,79 1,11 1,48 1,48Coil connections 1/2 1/2 3/4 3/4

    Speed connectedH V3 V3 V3 V3M V2 V2 V2 V2L V1 V1 V1 V1

    Power supply 230V/1/50HzH max. speed; M med. speed; L min. speedHeating mode2 pipes system configuration(1) Room air temperature 20C b.s.; Inlet water temperature 70C; T water 10C2 pipes system configuration (EUROVENT)(2) Room air temperature 20C b.s.; Inlet water temperature 50C; Water flow rate as in cooling modeCooling mode (EUROVENT)(3) Room air temperature 27C b.s./19C b.u.; Inlet water temperature 7C; T water 5C(4) Sound power level on the basis of measurements made in compliance with Eurovent 8/2(5) Sound pressure level (A-weighted) measured in the room with volume V=85m3, reverberation time t = 0.5 s; Direction factor Q = 2; Distance r = 2.5mNote: For more information, please refer to the program selection and the technical documentation available on the website www.aermec.com

    Dimensions (mm) CB

    D

    A

    B

    C

    A

    B

    A

    D

    C

    A

    B

    C

    Mod DUALJET 20 30 40 50Height

    Amm 520 520 520 520

    Height with feet mm 606 606 606 606Widht B mm 750 980 1200 1200Depth C mm 220 220 220 220

    D mm 88 88 88 88Weight (1) kg 15 20 24 24

  • 22

    Aermecparticipate in the EUROVENT program: FCHthe products are present on the sitewww.eurovent-certification.com

    Fan coilsUniversal installations for residential applicationsOmnia HL

    HL (High Line) fan coils for both horizontal and vertical installation

    4 sizes and 12 versions: HL: white body with switch HL M: metallic grey body with switch HL N: white body with electronic thermostat VMF HL NM: metallic grey body with electronic thermostat

    VMF HL L: white cabinet with Self-Closing Louver

    and electronic thermostat HL LM: grey cabinet with Self-Closing Louver

    and electronic thermostat HL PC: white body with electronic thermostat

    and Plasmacluster filter (factory-mounted only) HL PCM: metallic grey body with electronic

    thermostat and Plasmacluster filter (factory-mounted only)

    HL S: white body with no on-board controls VMF System compatible

    HL SM: metallic grey body with no on-board controls. VMF System compatible

    3-speed centrifugal fan Very quiet operation Aesthetically styled with soft flowing lines New adjustable air delivery louver Automatic power-off function with closure of

    the air delivery louver Slim dimensions Electronic temperature control, automatic fan

    speed change, automatic season changeover and automatic on - off (with electronic thermostat)

    Water connections reversibility during installation Low pressure drop across heat exchanger Motors with permanently connected condensers Easy installation and maintenance Full compliance with safety regulations

    Features

    Accessories

    Plasmacluster(only for Omnia HL PC and PCM)

    Versions compatible with VMF System. Fan cleaning: Omnia fan coils allow fan

    blades to be easily cleaned. It is now possible to remove the fan volute (it contains the fan blades) and clean it periodically.

    Condensate drip tray cleaning: Thanks to a new drip tray fitting, it is now easier to clean it with Omnia fan coils. This important solu-tion avoids, in the long run, bacteria, germs and mould to grow up, in the drip tray because of the air humidity.

    Precharged electrostatic filter: Omnia fan coils have, as standard, precharged electro-static filters. These filters, thanks to their spe-cial execution, attracts and retains all sus-pended dust particles, thus garanteeing pure breathable air to the whole family.

    PLASMACLUSTER ionising filter: Plasmacluster is capable of reducing the level of pollutants, by decomposing the molecules that form them. Using a series of electric shocks, "Plasmacluster" causes the water mol-

    ecules present in the air to separate into posi-tive and negative ions. These ions neutralise the gas pollutant molecules, forming products that are normally present in clean air. The result is in the air: you can finally breath clean, odour-free ionised air.

    Silent operation: Thanks to the use of special centrifugal fans, Omnia fan coils operation is extremely silent and offers the maximum acoustic comfort.

    Main features

    AMP: Kit for wall/ceiling mounting. Standard on S and SM versions.

    BC: Auxiliary condensate drip tray. BC 10 for vertical installation BC 20 for horizontal installation DSC5: Condensate drainage device for use

    when natural run-off is not possible. DSC5 is not compatible BC10 - BC20 accessories.

    PCH - PCHM: Back closing panel, white (PCHM) or gray (PCHM).

    SIT 3-5: Thermostat interface cards. They allow to set up a fancoils network (max. 10) commanded by a centralised panel (switch or thermostat).

    SIT3: commands the three speeds of the fan and must be installed on each fancoil of the network; it receives the commands from the switch or from the SIT5 card.

    SIT5: commands the 3 fan speeds and up to two valves (four-pipe systems); it sends the thermostat commands to the fancoils network.

    SW: Water probe which enables automatic season change-over thanks to the specific electronic thermostats.

    SWA: External probe accessory SWA (length L=6m). It detects the temperature of the room air if connected to the connector (A) of the FMT21 panel. The room air temperature probe, incorporated in the panel, is automatically disa-bled. It detects the temperature of the water in the system for ventilation consent if connected to the connector (W) of the FMT21 panel. Two SWA probes can be connected simultaneously to the FMT21 panel.

    VCH: Kit comprising motorized 3-way valve, unions and copper pipes.

    VCHD: Kit comprising motorized 2-way valve, unions and copper pipes.

    ZH1: White feet for floor-standing installations ZH1B: White feet for floor-standing installa-

    tions with skirting board. ZH1M: Gray feet for floor-standing installations ZH1MB: Gray feet for floor-standing installa-

    tions with skirting board. Control panels(1) and VMF system(2): the

    characteristics of the control panels are described on the appropriate card. PX2C6, PX2 panel in multiple 6-piece pack.

    * = The DSC5 accessory is not compatible BC10 - BC20 accessories.

    Compatibility of accessoriesOmnia HL 11 16 26 36 VersionsFMT10(1)FMT21(1) S-SMPX2(1) PX2C6(1) S-SMPXAE(1) S-SMTPF(1) S-SMWMT05(1) WMT10(1) S-SMVMF-E4(2) VMF-E4D(2) S-SMVMF-E2H(2) S-SMVMF-E0(2) VMF-E1(2) S-SMAMP 10 All except S, SMBC10 * AllBC20 * AllDSC5 * AllPCH/PCHM AllSIT3 S-SMSIT5 S-SMSW3 S-SMSWA S-SMVCH All except L, LMVCHD All except L, LMZH1/ZH1B AllZH1M/ZH1MB All

    White colour:cover: RAL 9002top and supports: RAL 7044

    Grey colour:cover: FIAT 656top and supports: RAL 7031

  • Aermec S.p.A.Via Roma, 996 - 37040 Bevilacqua (VR) - ItalyTel. +39 04 42 63 31 11 - Telefax +39 044 29 3577www.aermec.com

    23Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data.

    Cod

    .: SO

    HLU

    Y.18

    / 15

    02

    Technical data

    Dimensions (mm)

    Mod Omnia HL 11 HL 16 HL 26 HL 36Height A 600 605 615 623Widht B 640 750 980 1200Depth C 187 189 191 198Height with feet D 93 93 93 93Weight kg 13,6 14,6 17,6 20,6

    Mod. Vel. HL 11 HL 16 HL 26 HL 36HEATING PERFORMANCE (2 PIPE CONFIGURATION)

    Heating capacity (70C)(1) W H 2010 2910 4620 5940(1) W M 1460 2120 3830 4870(1) W L 1060 1540 2890 3530

    Water flow rate(1) l/h H 176 255 405 521(1) l/h M 128 186 336 427(1) l/h L 93 135 253 310

    Pressure drop(1) kPa H 2 4 11 7,7(1) kPa M 1 2 8 5,4(1) kPa L 1 1 5 3

    Heating capacity (50C)(2) W H 1150 1700 2750 3540(2) W M 870 1250 2240 2860(2) W L 650 930 1670 2080

    Water flow rate(2) l/h H 144 206 349 487(2) l/h M 117 153 289 394(2) l/h L 93 122 220 286

    Pressure drop(2) kPa H 2 4 10 16(2) kPa M 1 2 7 11(2) kPa L 1 2 4 6

    HEATING PERFORMANCE (2 PIPE CONFIGURATION)

    Total cooling capacity(3) W H 840 1200 2030 2830(3) W M 680 890 1680 2290(3) W L 540 710 1280 1660

    Sensible cooling capacity(3) W H 700 990 1640 2040(3) W M 530 710 1330 1620(3) W L 390 540 990 1160

    Water flow rate (3) l/h H 144 206 349 487(3) l/h M 117 153 289 394(3) l/h L 93 122 220 286

    Pressure drop(3) kPa H 1,9 4,8 11 18,9(3) kPa M 1 3 9 12(3) kPa L 1 2 5 7

    Air flow ratem3/h H 180 240 350 460m3/h M 120 160 270 350m3/h L 80 110 190 240

    Fanstype Centrifugaln 1 1 2 2

    Absorbed powerW H 18 32 35 42W M 12 25 27 35W L 8 23 24 30

    Max. input current (A) 0,09 0,15 0,18 0,22

    Sound power level(4) dB(A) H 46 48 48 50(4) dB(A) M 37 43 43 43(4) dB(A) L 31 34 35 34

    Sound pressure level(5) dB(A) H 37,5 39,5 39,5 39,5(5) dB(A) M 28,5 34,5 34,5 32,5(5) dB(A) L 22,5 25,5 26,5 25,5

    Water content l 0,4 0,5 0,8 1,1Coil connections 1/2" 1/2" 1/2" 1/2"

    Speed connectedH V3 V3 V3 V3M V2 V2 V2 V2L V1 V1 V1 V1

    Power supply 230V/1/50Hz

    H max. speed; M med. speed; L min. speedHeating mode2 pipes system configuration(1) Room air temperature 20C b.s.; Inlet water temperature 70C; DT water 10C2 pipes system configuration (EUROVENT)(2) Room air temperature 20C b.s.; Inlet water temperature 50C; Water flow rate as in cooling modeCooling mode (EUROVENT)(3) Room air temperature 27C b.s./19C b.u.; Inlet water temperature 7C; T water 5C(4) Sound power level on the basis of measurements made in compliance with Eurovent 8/2(5) Sound pressure level (A-weighted) measured in the room with volume V=85m3, reverberation time t = 0.5 s; Direction factor Q = 2; Distance r = 2.5mNote: For more information, please refer to the program selection and the technical documentation available on the website www.aermec.com

  • 24

    Aermecparticipate in the EUROVENTprogram: FCHthe products are present on the sitewww.eurovent-certification.com

    Fan coilsUniversal installations for residential applicationsOmnia UL

    AMP: Kit for wall/ceiling mounting. Standard on P and S versions.

    BC: Auxiliary condensate drip tray. BC 10 for vertical installation BC 20 for horizontal installation DSC5: Condensate drainage device for use

    when natural run-off is not possible. DSC5 is not compatible BC10 - BC20 accessories.

    GU: Aspiration grille, covers the front space between the stands, does not interfere with the air filter. Use with ZU stands compulsory.

    PCU: Rear cover panel. SIT 3-5: Thermostat interface cards. They

    allow to set up a fancoils network (max. 10) commanded by a centralised panel (switch or thermostat).

    SIT3: commands the three speeds of the fan and must be installed on each fancoil of the network; it receives the commands from the switch or from the SIT5 card.

    SIT5: commands the 3 fan speeds and up to two valves (four-pipe systems); it sends the thermostat commands to the fancoils net-work.

    SW: Water probe wich enables automatic season change-over thanks to the specific electronic thermostats.

    SWA: External probe accessory SWA (length L = 6m). It detects the temperature of the room air if connected to the connector (A) of the FMT21 panel. The room air temperature probe, incorporated in the panel, is automati-

    cally disabled. It detects the temperature of the water in the system for ventilation consent if connected to the connector (W) of the FMT21 panel. Two SWA probes can be con-nected simultaneously to the FMT21 panel.

    VCH: Kit comprising motorized 3-way valve, unions and copper pipes.

    VCHD: Kit comprising motorized 2-way valve, unions and copper pipes.

    ZU: Feet for floor-standing solutions. Control panels and VMF System: The control

    panels are described in a separate document.

    Accessories

    UL (Universal Line) fan coils for both hori-zontal and vertical installation

    Versions: UL-S: version without switch, with cabinet.

    Compatible with VMF System UL: version with switch and cabinet UL-C: version with electronic thermostat and

    with cabinet UL-PC: version with electronic thermostat

    and Plasmacluster filter (factory-mounted only) and cabinet

    Versions compatible with VMF System. Fan cleaning: Omnia fan coils allow fan

    blades to be easily cleaned. It is now possible to remove the fan volute (it contains the fan blades) and clean it periodically.

    Condensate drip tray cleaning: Thanks to a new drip tray fitting, it is now easier to clean it with Omnia fan coils. This important solu-tion avoids, in the long run, bacteria, germs and mould to grow up, in the drip tray

    because of the air humidity. Precharged electrostatic filter: Omnia fan

    coils have, as standard, precharged electro-static filters. These filters, thanks to their spe-cial execution, attracts and retains all sus-pended dust particles, thus garanteeing pure breathable air to the whole family.

    PLASMACLUSTER ionising filter: Plasmacluster is capable of reducing the level of pollutants, by decomposing the molecules that form them. Using a series of electric shocks, "Plasmacluster" causes the water mol-ecules present in the air to separate into posi-tive and negative ions. These ions neutralise the gas pollutant molecules, forming products that are normally present in clean air. The result is in the air: you can finally breath clean, odour-free ionised air.

    Silent operation: Thanks to the use of special centrifugal fans, Omnia fan coils operation is extremely silent and offers the maximum

    acoustic comfort. 3-speed centrifugal fan Very quiet operation Aesthetically styled with soft flowing lines Adjustable air delivery louver Automatic power-off function with closure of

    the air delivery louver Slim dimensions Electronic temperature control, automatic fan

    speed change, automatic season changeover and automatic on - off (with electronic ther-mostat)

    Water connections reversibility during instal-lation

    Low pressure drop across heat exchanger Motors with permanently connected conden-

    sers Easy installation and maintenance Air filter easy to remove and to clean Full compliance with safety regulations

    Features

    Plasmacluster(only for Omnia UL PC)

    (1) PX2C6, PX2 panel in multiple 6-piece pack.(2) The DSC5 accessory is not compatible BC10 - BC20 accessories.

    White colour:cover: RAL 9002top and supports: RAL 7044

    Omnia UL_S_C_PC vers. 11 16 26 36FMT21 S PX2 o PX2C6 (1) S PXAE S PXLM S TPF S WMT05 S WMT10 S VMF-E4 o E4D S VMF-E0 o E1 S AMP10 UL-C-PC BC10 all BC20 all DSC5 (2) all SIT3 S SIT5 S SW3 all SWA S VCH all VCHD all ZU UL-S-C-PC

  • Aermec S.p.A.Via Roma, 996 - 37040 Bevilacqua (VR) - ItalyTel. 0442633111 - Telefax 044293730www.aermec.com

    25Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data.

    Cod

    .: SO

    ULU

    Y.17

    / 150

    2

    Technical dataMod. Vel. UL11 UL16 UL26 UL36HEATING PERFORMANCE (2 PIPE CONFIGURATION)

    Heating capacity (70C)(1) W H 2010 2910 4620 5940(1) W M 1460 2120 3830 4870(1) W L 1060 1540 2890 3530

    Water flow rate(1) l/h H 176 255 405 521(1) l/h M 128 186 336 427(1) l/h L 93 135 253 310

    Pressure drop(1) kPa H 2 4 11 7,7(1) kPa M 1 2 8 5,4(1) kPa L 1 1 5 3

    Heating capacity (50C)(2) W H 1150 1700 2750 3540(2) W M 870 1250 2240 2860(2) W L 650 930 1670 2080

    Water flow rate(2) l/h H 144 206 349 487(2) l/h M 117 153 289 394(2) l/h L 93 122 220 286

    Pressure drop(2) kPa H 2 4 10 16(2) kPa M 1 2 7 11(2) kPa L 1 2 4 6

    COOLING PERFORMANCE

    Total cooling capacity(3) W H 840 1200 2030 2830(3) W M 680 890 1680 2290(3) W L 540 710 1280 1660

    Sensible cooling capacity(3) W H 700 990 1640 2040(3) W M 530 710 1330 1620(3) W L 390 540 990 1160

    Water flow rate (3) l/h H 144 206 349 487(3) l/h M 117 153 289 394(3) l/h L 93 122 220 286

    Pressure drop(3) kPa H 1,9 4,8 11 18,9(3) kPa M 1 3 9 12(3) kPa L 1 2 5 7

    Air flow ratem3/h H 180 240 350 460m3/h M 120 160 270 350m3/h L 80 110 190 240

    Fanstype Centrifugaln 1 1 2 2

    Absorbed powerW H 18 32 35 42W M 12 25 27 35W L 8 23 24 30

    Max. input current (A) 0,09 0,15 0,18 0,22

    Sound power level(4) dB(A) H 46 48 48 50(4) dB(A) M 37 43 43 43(4) dB(A) L 31 34 35 34

    Sound pressure level(5) dB(A) H 37,5 39,5 39,5 39,5(5) dB(A) M 28,5 34,5 34,5 32,5(5) dB(A) L 22,5 25,5 26,5 25,5

    Water content l 0,4 0,5 0,8 1,1Coil connections 1/2" 1/2" 1/2" 1/2"

    Speed connectedH V3 V3 V3 V3M V2 V2 V2 V2L V1 V1 V1 V1

    Power supply 230V/1/50Hz

    H max. speed; M med. speed; L min. speedHeating mode2 pipes system configuration(1) Room air temperature 20C b.s.; Inlet water temperature 70C; T water 10C2 pipes system configuration (EUROVENT)(2) Room air temperature 20C b.s.; Inlet water temperature 50C; Water flow rate as in cooling modeCooling mode (EUROVENT)(3) Room air temperature 27C b.s./19C b.u.; Inlet water temperature 7C; T water 5C(4) Sound power level on the basis of measurements made in compliance with Eurovent 8/2(5) Sound pressure level (A-weighted) measured in the room with volume V=85m3, reverberation time t = 0.5 s; Direction factor Q = 2; Distance r = 2.5mNote: For more information, please refer to the program selection and the technical documentation available on the website www.aermec.com

    Mod Omnia UL 11 UL 16 UL 26 UL 36Height A 513 513 513 513Widht B 640 750 980 1200Depth C 173 173 173 173Height with feet D 93 93 93 93Weight kg 12,5 13,5 16,5 19,5

    A

    BC

    A

    D

    ZU

    BC

    Wall installation Floor installation

    Dimensions (mm)

  • 26

    Fan coils with radiant panel for residential use Ceiling or floor mounted

    Omnia Radiant

    Omnia Radiant and Omnia Radiant Plus Aermec innovative solutions In this particular worldwide market evolution, we are pleased to present to you OMNIA Radiant, which represents the innovation of the OMNIA AERMEC series, fan coils especially designed for residential comfort.

    OMNIA Radiant inherits all the advantages of the OMNIA UL series, and is characterized by the introduction of the frontal plate for radiant heating.OMNIA Radiant Plus is provided with the DC Brushless electric engine, equipped with the latest Inverter technology, granting the highest energy efficiency and able to regulate the air flow through the continuous fan speed modula-tion. This allows to achieve up to 60% in energy saving when compared to the traditional On-Off fan system, in both air conditioning and heating.

    OMNIA Radiant and Radiant Plus offer the fol-lowing advantages when compared to the tradi-tional systems: the radiant plate combination the finned

    coil allows the best winter comfort with the lower energy consumption because it provi-des heating with lower water temperature: only 45C against the about 65C needed for the traditional radiator. This not only increases the comfort for the user, but also significantly increases the overall efficiency in case of heat pumps usage;

    the fan system allows to quickly reach the desired temperature, meeting the require-ment of a fast start-up;

    the unit can be combined other than the boiler, also to energy saving heat pumps: air to water, water to water and geothermic type;

    the electrostatic charge filter standard sup-plied, provides pure and clean air;

    during summer Omnia Radiant and Radiant Plus provide air conditioning and dehumidi-fication in a fast and efficient way in every room.

    The four different working modes of Omnia Radiant annual functioning

    Radiant: Heating through radiation, comfortable and noiseless, is granted by the radiant plate pla-ced on the front of the fan coil cover; if necessa-ry, the triple-fins delivery head can be closed to increases the heating of the plate, thus maximi-zing the radiant effect.

    Radiant + Natural Convection With the triple-fins open, heating through natu-ral convection, obtained thanks to the bigger coil exchange surface, is added to the radiant heating.As for the radiant-only mode (see above), the fan groups are in off mode. This results in acoustic comfort and energy saving.

    Radiant + Forced ConvectionThe electronic regulation, precise and reliable, continuously compares the effective indoor tem-perature with the desired temperature: whenever the difference between the two should prove to be too high (e.g. during the heating system start-up) the software will lead the fan system start-up. Start-up is fast and efficient and grants significant energy savings especially in rooms that are occa-sionally used.

    Omnia Radiant during summer provides air conditioning and dehumidification:

    Forced ConvectionDuring summer, Omnia Radiant and Radiant Plus provide air conditioning and dehumidifica-tion for each room of the house in a fast and effi-cient way. Efficiency and quietness benefit from the quality that has always characterized the Omnia series.

    Features

    Radiant

    Radiant + Natural Convection

    Radiant + Forced Convection

    Forced Convection

    Aermecparticipate in the EUROVENT program: FCUthe products are present on the sitewww.eurovent-certification.com

    LOW TEMPERATURE RADIATION* VENTILATED HEATING COOLING - DEHUMIDIFICATION ENERGY SAVING LOW OPERATING COST

    * Radiant technology under licence

  • 27

    OMNIA radiant (UL_R) standard features: - Radiant panel - Centrifugal fans - Three-speed motor - Condensate storage container, hydraulic

    hoses - Switching valve - Water probe - Electro-statically preloaded filter - VMF-thermostat for asynchronous motor - Compatible with VMF system

    OMNIA radiant plus (UL_RI) standard fea-tures:

    - Radiant panel - Centrifugal fans - Electric DC Brushless motor with Inverter - Condensate storage container, hydraulic hoses - Water probe - Switching valve - Electro-statically preloaded filter - VMF thermostat for DC Brushless motor - Compatible with VMF system

    Cleaning the fan: The fan blades on the Omnia Radiant are easy to clean. As a mat-ter of fact, the new versions now offer the possibility of opening the worm screw of the fan (the casing that encloses the blades) to perform routine cleaning.

    Electro-statically preloaded filter: The Omnia Radiant fan coils feature standard air filters that are electro-statically preloa-ded. These filters, thanks to their particular construction, absorb and trap floating dust: the ideal system to provide clean air for all the family.

    Silent operation: Thanks to special centrifu-gal fans, Omnia Radiant fan coils are incre-dibly silent, making them the best buy when it comes to acoustic comfort, given the total lack of peak noise. "The heating by radiation at top speed ensures total silence regime

    Note:The coil had hydraulic hoses on the left and is not reversible.

    Features of the Omnia Radiant series

    Accessories

    1

    2

    3

    4

    Radiant plate

    Switching valve

    Water probe

    Condensate storage container, hydraulic hoses

    1

    2

    3

    4

    PCU: Rear closing panel. ZU: Wedges for floor mount. GU: Exhaust grille: covers the front space of

    the wedges and does not interfere with the air filter.

    VCHRAD: Kit comprising motorized 3-way valve, unions and copper pipes.

    Must be combined with ZU wedges. VMF System: Its specs are described in its technical sheet.

    Omnia radiant Omnia Radiant plusUL26R UL36R UL26RI UL36RI

    PCU 25 35 25 35

    GU 25 35 25 35

    VCHRAD

    ZU

    VMF systemVMF-E4 (compulsory accessory)

    VMF-E4D (compulsory accessory)

    VMF-E5B * *

    VMF-E5N * *

    * Contact us

    3

    VCHRAD accessory

  • 28

    Technical Data

    Cooling: Room temperature 27C b.s./19C b.u.; Cold water (in/out) 7C/12CHeating: (1) Room temperature 20C b.s.; Hot water (in) 70C; T 10C(2) Room temperature 20C b.s.; Hot water (in/*) 50C/*C (water flow same as in heating cycle)(3) Radiant power + natural convection; Hot water (in) 70C (water flow same as in heating cycle)(4) Radiant power + natural convection; Hot water (in/*) 50C/*C (water flow same as in heating cycle)(5) Radiant power + natural convection; Hot water (in/*) 35C/*C (water flow same as in heating cycle)

    Mod. UL_R 26 36

    Heating capacity (70C) (1)W (max.) 4620 5940W (med.) 3830 4870W (min.) 2890 3530

    Heating capacity (50C) (2) W 2750 3540Water flow rate l/h 397 511Water pressure drop kPa 17 21Static heating power (70C) (3) W 650 750Static heating power (50C) (4) W 390 450Static heating power (35C) (5) W 200 230

    Total cooling capacityW (max.) 2030 2830W (med.) 1780 2310W (min.) 1420 1730

    Sensible cooling capacityW (max.) 1640 2040W (med.) 1370 1790W (min.) 1050 1280

    Water flow rate l/h 349 487Water pressure drop kPa 18 22

    Air flow ratem3/h (max.) 350 460m3/h (med.) 270 350m3/h (min.) 190 240

    n Fans n. 2 2

    Sound pressuredB (A) (max.) 39,5 39,5dB (A) (med.) 34,5 32,5dB (A) (min.) 26,5 25,5

    Sound powerdB (A) (max.) 48 50dB (A) (med.) 43 41dB (A) (min.) 35 34

    Water contents l 0,8 1,1Max. motor power W 35 42Max. input current A 0,18 0,22Coil connections (in/out) (mm) 14 14Power supply V/ph/Hz 230V/1/50Hz 230V/1/50Hz

    Mod. UL_RI 26 36

    Heating capacity (70C) (1)W (max.) 4620 5940W (med.) 3830 4870W (min.) 2890 3530

    Heating capacity (50C) (2) W 2750 3540Water flow rate l/h 397 511Water pressure drop kPa 17 21Static heating power (70C) (3) W 650 750Static heating power (50C) (4) W 390 450Static heating power (35C) (5) W 200 230

    Total cooling capacityW (max.) 2030 2830W (med.) 1780 2310W (min.) 1420 1730

    Sensible cooling capacityW (max.) 1640 2040W (med.) 1370 1790W (min.) 1050 1280

    Water flow rate l/h 349 487Water pressure drop kPa 18 22

    Air flow ratem3/h (max.) 350 460m3/h (med.) 270 350m3/h (min.) 190 240

    n Fans n. 2 2

    Sound pressuredB (A) (max.) 39,5 39,5dB (A) (med.) 34,5 32,5dB (A) (min.) 26,5 25,5

    Sound powerdB (A) (max.) 48 50dB (A) (med.) 43 41dB (A) (min.) 35 34

    Water contents l 0,8 1,1Max. motor power W 12 16Max. input current A 0,18 0,22Coil connections (in/out) (mm) 14 14Power supply V/ph/Hz 230V/1/50Hz 230V/1/50Hz

    Level of sound pressure (A-weighted) measured in the room with volume V = 85m3 ; reverberation time t = 0.5s; direction factor Q = 2; distance r = 2.5m

  • 29Aermec S.p.A.Via Roma, 996 - 37040 Bevilacqua (VR) - ItaliaTel. 0442633111 - Telefax 044293577www.aermec.com

    Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data.

    Heating capacity with fan off

    Dimensions (mm)

    A

    BC

    A

    D

    ZU

    BC

    Mod OMNIA ULR - ULRI 26 36Height A (mm) 606 606Width B (mm) 980 1200Depth C (mm) 173 173Height with ZU (Accessories) D (mm) 93 93Weight (1) (kg) 20 24

    (1) Standard configuration of unit with accessories

    Wall installation

    Floor installation

    Cod

    .: SO

    ULR

    _RIU

    Y.03

    / 14

    11

    UL26R - UL26RI

    UL36R - UL36RI

    Hea

    ting

    cap

    acit

    y [W

    ]H

    eati

    ng c

    apac

    ity

    [W]

    Roo

    m t

    empe

    ratu

    re [

    C]

    Roo

    m t

    empe

    ratu

    re [

    C]

    Inlet water temperature [C]

    Inlet water temperature [C]

    20C18C16C

    22C24C26C

    30 35 40 45 50 55 60 65 70 75 800

    100

    200

    300

    400

    500

    600

    700

    800

    900

    20C18C16C

    22C24C26C

    0

    100

    200

    300

    400

    500

    600

    35 40 45 50 55 60 65 70

  • 30

    Fan coilsDuct installationFCX P

    Vertical and horizontal installation:FCX P: Duct installation without cabinetFCX PPC: Duct installation without cabinet, with Plasmacluster purifier. Compatible with the VMF system, or you can request a combination with the PXAE control panelFCX PE: Duct installation without cabinet and with direct expansion coilFCX PO: with boosted motor6-speed (3 of which can be selected) up 22 to 82 7-speed (3 of which can be selected) up 62 to 82FCX PBV: with 3 row coil +1 in a single shoulder, standard connections (left)FCX PBVD: with 3 row coil +1 in a single shoul-

    der, standard connections (right)FCX POBV: boosted and with 3 row coil +1 in a single shoulder, standard connections (left)FCX POBVD: boosted and with 3 row coil +1 in a single shoulder, standard connections (right)For versions with 3 row +1 battery, the battery is not reversible specify the side of the attacks at the time of the order. - Vertical installation:FCX PV: Duct installation without cabinet Versions with 3/4-row coil 3-speed ventilating unit Compatible with the VMF system Wide range of controls and accessories

    Quiet operation Low loss of charge in batteries Electric motors with permanently inserted

    condensers Ease of installation and maintenance Air filter easy to remove and clean Possibility of a residual head for ducting (if

    required) Internal insulation and air filter in fire resist-

    ance class 1 Extractable shrouds for easy, effective cleaning Water connections can be reversed during

    installation phase

    Features

    AMP: Kit for overhang installation. BC: Auxiliary condensate drip tray. BV: 1-row hot water coil. Not available for

    4-row versions or those with Plasmacluster. When mounted in place, you must specify the con-

    nection side CHF:VentilCassaforma is a galvanised metal

    template that allows you to create a space directly in the wall for housing the fan coil. (For FCX P - PV only).

    DSC4: Condensate drainage device for use when natural run-off is not possible.

    GA: Intake grille with fixed fins. GAF: Intake grille with fixed fins and filter. GM: Delivery grille with adjustable fins. MA: A-type covering cabinet (use tray acces-

    sory BC 4 for FCX AS). MU: U-type covering cabinet (use the BC 5-6

    tray accessory if horizontal, or BC 4 if vertical). PCR: Galvanised plate protection for the con-

    trols and the electrical element. PA: Plenum suction assembly in galvanised

    sheet metal, complete with suction couplings for circular-section ducts.

    PA-F: Plenum suction assembly that allows intake and delivery on the same side; suitable for all installations where the machine needs to be positioned outside the air-conditioned

    rooms in order to minimise noise levels and facilitate maintenance operations.

    PM: Delivery plenum in galvanised sheet metal, externally insulated, complete with plastic delivery couplings for circular section ducts.

    RD: Straight delivery coupling for canalisation. RDA: Straight suction coupling for canalisation. RP: 90 delivery coupling for canalisation. RPA: 90 suction coupling for canalisation. RX: Armoured electric coil with safety ther-

    mostat. (Requires a thermostat with heater management). Not available for 4-row ver-sions or those with Plasmacluster.

    SE: Manually operated fresh air intake louver. SIT 3 - 5: Thermostat Interface Cards. They

    allow the creation of a network of fan coils (max. 10) commanded by a central control panel (selector or thermostat).

    SIT3: commands the 3 fan speeds and must be installed on each fan coil of the network; receives the commands from the selector or the SIT5 card.

    SIT5: commands the 3 fan speeds and up to 2 valves (four pipes systems); sends the com-mands of the thermostat to the fan coils net-work.

    SW: water temperature probe that gives the auto-matic season change feature to electronic thermo-

    stats supplied with water-side change over. SWA: External probe accessory SWA (length L = 6m). It

    detects the temperature of air or water depending on its location in the plant

    VCF: the kit contains a motorised 3-way valve with insulating shell, plus coupling and pipes in insulated copper. For 4-row, 3-row and 1-row coils (BV). Versions with 230V and 24V~50Hz power supply

    VCFD: Kit consisting of powered 2-way valve, copper couplings and pipes. For 4-row, 3-row and 1-row coils (BV). Versions with 230V and 24V~50Hz power supply.

    VCF_X4: The valve kits are designed for fan coil units with single coil, installed in a 4 pipe system with the "Cooling" and "Heating" circuits totally separated. The kit consists of 2 valves of 3-way 4 port connection complete with electro-thermal actuators, insulating shells for the valves and associated hydraulic piping. VCF1X4L Valve kit for left hand con-nection fan coil units. VCF1X4R Valve kit for right hand connection fan coil units. Power supply: 230V ~ 50Hz.

    ZX: Feet for recessed installation.

    Control panels and VMF System: the character-istics are described on the appropriate card.

    Accessories

    VERSION AVAILABLE SIZESVersions with 3 row coil Versions with 4 row coil

    FCX_P 17 22 32 36 42 50 56 62 82 102 24 34 44 54 64 84FCX_PV 17 22 32 36 42 50 56 62 82 102 24 34 44 54 64 84FCX_PO - 22 32 36 42 50 56 62 82 - 24 34 44 54 64 84FCX_PE - 22 32 - 42 50 - 62 82 102 - - - - - -FCX_PPC - 22 32 36 42 50 56 62 82 - 24 34 44 54 64 84FCX_PBV 17 22 32 36 42 50 56 62 82 102 - - - - - -FCX_PBVD 17 22 32 36 42 50 56 62 82 102 - - - - - -FCX_POBV - 22 32 36 42 50 56 62 82 - - - - - - -FCX_POBVD - 22 32 36 42 50 56 62 82 - - - - - - -

    Aermecparticipate in the EUROVENTprogram: FCUthe products are present on the sitewww.eurovent-certification.com

  • 31

    FCX Fan CoilAccessories 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102 VersionsFMT10 FMT21 (1) P-PE-PO-PVKTLP (1) P-PE-PO-PVPX PX2 PX2C6 (1) P-PE-PO-PVPXAE (1) P-PE-PO-PV-PPCPXAR (1) P-PE-PO-PVTF1 (1) P-PE-PO-PVTPF (1) P-PE-PO-PVWMT05 WMT06 WMT10 (1) P-PE-PO-PVVMF-E4 VMF-E4D (1) P-PE-PO-PVVMF-E0 VMF-E1AMP P-PE-PO-PPCAMP20 P-PE-PO-PPC

    BC

    4 (2) FCX P-PV+ MA5 FCX P + MU6 FCX P + MU8 P-PE-PO-PPC9 P-PE-PO-PPC

    BV

    117 P-PE-PV122 P-PE-PO-PV132 P-PE-PO-PV142 P-PE-PO-PV162 P-PE-PO-PV

    CHF

    17 P-PV22 P-PV32 P-PV42 P-PV62 P-PV

    DSC4 (3) P-PE-PO-PV-PPC

    GA

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    GAF

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    GM

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    MA

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    MU

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    PA

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    PA

    17 F P-PE-PV-PPC22 F P-PE-PO-PV-PPC32 F P-PE-PO-PV-PPC42 F P-PE-PO-PV-PPC62 F P-PE-PO-PV-PPC

    PCR 1 P-PE-PO-PV-PPC2 P-PE-PO-PV-PPC

    PM

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    RD

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    RDA

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    RP

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PV-PPC

    RPA

    17 P-PE-PV-PPC22 P-PE-PO-PV-PPC32 P-PE-PO-PV-PPC42 P-PE-PO-PV-PPC62 P-PE-PO-PPC

    RX

    17 P-PE-PV22 P-PE-PO-PV32 P-PE-PO-PV42 P-PE-PO-PV52 P-PE-PO-PV62 P-PE-PO-PV

  • 32

    Technical data

    FCX Fan CoilAccessories 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102 Versions

    SE

    15X (4) P-PE-PV20X (4) P-PE-PO-PV-PPC30X (4) P-PE-PO-PV-PPC40X (4) P-PE-PO-PV-PPC80X (4) P-PE-PO-PV-PPC

    SIT 3 P-PE-PO-PV5 P-PE-PO-PV-PPCSW3 P-PO-PVSWA P-PO-PV

    VCF

    1X4L - 1X4R P-PO-PV2X4L - 2X4R P-PO-PV3X4L - 3X4R P-PO-PV41 - 4124 (5) P-PO-PV-PPC42 - 4224 (5) P-PO-PV-PPC43 - 4324 (5) P-PO-PV-PPC44 - 4424 (5)(6) P-PO-PV45 - 4524 (5) P-PO-PV

    VCFD

    1 - 124 (5) P-PO-PV-PPC2 - 224 (5) P-PO-PV-PPC3 - 324 (5) P-PO-PV-PPC4 - 424 (5)(7) P-PO-PV

    ZX 7 P-PE-PO-PV-PPC8 P-PE-PO-PV-PPC

    (1) the characteristics are described on the appropriate card.(2) Accessories and BC4 VCF can not be mounted at the same time(3) DSC4 is incompatible with the accessory AMP and BC Auxiliary condensate

    drip tray

    (4) The accessory SE require pairing with ZX(5) 24 Volt(6) Only for the BV1-row coil accessory

    Mod. FCX_P / FCX_PO Vel. 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102HEATING PERFORMANCE (2 PIPE CONFIGURATION)

    Heating capacity (70C)(1) W H 2296 2960 3912 5354 5964 6413 6618 8600 8191 10100 9648 12919 14300 15140 17100 17019(1) W M 2033 2531 3103 4065 4801 4983 5521 6930 7529 8759 8434 10942 11501 13349 14421 15242(1) W L 1686 1906 2097 3165 3728 4188 4062 5200 5021 6241 6056 8327 8499 10771 11198 12558

    Water flow rate(1) l/h H 201 260 343 470 523 563 581 754 718 886 846 1133 1254 1328 1500 1493(1) l/h M 178 222 272 357 421 437 484 608 660 768 740 960 1009 1171 1295 1337(1) l/h L 148 167 184 278 327 367 356 456 440 547 531 730 745 945 982 1101

    Pressure drop(1) kPa H 3 6 4 20 11 13 15 22 15 23 42 17 23 21 32 43(1) kPa M 2 4 3 12 7 10 11 15 13 18 33 12 16 16 23 34(1) kPa L 1 3 1 8 5 8 6 9 6 9 19 7 9 11 15 24

    Heating capacity (50C)(2) W H 1360 1770 2320 3160 3550 3800 3960 4950 4870 6100 5380 7500 8400 7960 10200 10000(2) W M 1200 1510 1840 2400 2860 2950 3300 4140 4480 5220 4840 6430 6800 6860 8600 9000(2) W L 990 1130 1250 2060 2220 2480 2430 3170 3000 3700 3680 4880 5040 5200 6700 7440

    Water flow rate(2) l/h H 172 258 298 413 482 482 585 765 721 855 791 836 1092 1189 1479 1311(2) l/h M 144 210 236 316 392 370 478 617 604 743 662 752 896 860 1259 1183(2) l/h L 112 144 174 267 303 311 397 463 432 533 475 554 674 738 992 979

    Pressure drop(2) kPa H 2 6 3 16 9 9 15 23 15 22 22 9 18 21 31 33(2) kPa M 2 5 2 10 7 7 13 15 11 17 20 7 13 12 23 27(2) kPa L 1 2 1 7 4 6 8 9 6 9 15 4 8 9 15 19

    HEATING PERFORMANCE (4 PIPE CONFIGURATION - with additional heat exchanger)

    Heating capacity (70C)(3) W H 1400 1770 - 2850 - - 3460 - 4380 - - 5490 - 6410 - 6810(3) W M 1200 1510 - 2450 - - 3410 - 3940 - - 4700 - 6300 - 6230(3) W L 990 1130 - 2030 - - 2660 - 3220 - - 3870 - 5300 - 5430

    Water flow rate(3) l/h H 123 155 - 250 - - 303 - 384 - - 482 - 562 - 6809(3) l/h M 105 132 - 215 - - 299 - 346 - - 412 - 553 - 6232(3) l/h L 87 99 - 178 - - 233 - 282 - - 339 - 465 - 5428

    Pressure drop(3) kPa H 3 6 - 16 - - 21 - 35 - - 16 - 15 - 19(3) kPa M 2 5 - 12 - - 20 - 30 - - 12 - 14 - 16(3) kPa L 2 3 - 8 - - 14 - 21 - - 10 - 11 - 13

    COOLING PERFORMANCE (2 and 4 PIPE CONFIGURATIONS)

    Total cooling capacity(4) W H 1000 1500 1730 2400 2800 2800 3400 4450 4190 4970 4600 4860 6350 6910 8600 7620(4) W M 840 1220 1370 1840 2280 2150 2780 3590 3510 4320 3850 4370 5210 5000 7320 6880(4) W L 650 840 1010 1550 1760 1810 2310 2690 2510 3100 2760 3220 3920 4290 5770 5690

    Sensible cooling capacity(4) W H 830 1240 1380 1900 2130 2200 2760 3300 3000 3540 3500 3980 5030 5680 5780 5530(4) W M 690 1000 1090 1570 1720 1820 2110 2640 2540 3060 3070 3300 4100 3780 4870 5350(4) W L 510 670 760 1110 1250 1280 1630 1960 1790 2170 2120 2440 3060 2970 2800 4420

    Water flow rate (4) l/h H 172 258 298 413 482 482 585 765 721 855 791 836 1092 1189 1479 1311(4) l/h M 144 210 236 316 392 370 478 617 604 743 662 752 896 860 1259 1183(4) l/h L 112 144 174 267 303 311 397 463 432 533 475 554 674 738 992 979

    Pressure drop(4) kPa H 2,6 5,8 3 28 13,8 28 14,3 40,2 19,3 25,9 38 17,3 13 22 29,5 37,3(4) kPa M 2 5 2 17 10 17 10 27 14 21 28 14 9 12 22 31(4) kPa L 1,4 2,5 1 13 6 12,7 7 16,3 7,6 11,7 15,1 8,3 5,5 9,3 14,7 22

    Air flow ratem3/h H 200 290 290 450 450 450 600 600 720 720 720 920 920 1140 1140 1300m3/h M 160 220 220 350 350 350 460 460 600 600 600 720 720 930 930 1.120m3/h L 110 140 140 260 260 260 330 330 400 400 400 520 520 700 700 900

    Fanstype centrifugaln 1 1 1 2 2 2 2 2 2 2 2 3 3 3 3 3

    Absorbed powerW H 35 25 33 44 44 44 57 57 67 76 76 82 91 106 106 131W M 29 22 29 33 34 33 43 43 46 52 52 61 60 80 80 100W L 19 19 25 25 28 25 30 30 34 38 38 40 38 59 59 80

  • 33Aermec S.p.A.Via Roma, 996 - 37040 Bevilacqua (VR) - ItaliaTel. 0442633111 - Telefax 044293577www.aermec.com

    Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data.

    Cod

    .: SF

    CX

    PUY.

    16 /

    1401

    Mod. FCX_P / FCX_PO Vel. 17 22 24 32 34 36 42 44 50 54 56 62 64 82 84 102

    Max input current(P) (A) 0,16 0,12 0,25 0,21 0,45 0,21 0,28 0,51 0,35 0,36 0,35 0,4 0,48 0,49 0,62 0,58(PO) (A) - 0,25 0,25 0,45 0,45 0,45 0,51 0,51 0,36 0,36 0,36 0,48 0,48 0,62 0,62 -

    Sound power level (P)(5) dB(A) H 45 50 51 48 48 48 51 55 56 56 56 57 57 61 61 66(5) dB(A) M 38 43 46 41 41 41 44 50 51 53 51 51 51 56 57 61(5) dB(A) L 31 31 35 34 36 34 37 41 42 44 42 42 44 51 51 56

    Sound pressure level (P)(6) dB(A) H 37 42 43 40 40 40 43 47 48 48 48 49 49 53 53 58(6) dB(A) M 30 35 38 33 33 33 36 42 43 45 43 43 43 48 49 53(6) dB(A) L 23 23 27 26 28 26 29 33 34 36 34 34 36 43 43 48

    Sound power level (PO) (5) dB(A) H - 58 58 53 53 53 59 59 59 59 59 62 62 64 64 -Sound pressure level (PO) (6) dB(A) H - 50 50 44 44 44 50 50 51 51 51 54 54 56 56 -Water content l 0,58 0,79 1 1,11 1,5 1,5 1,48 1,9 1,48 1,9 1,9 2,52 3,4 2,52 3,4 2,52

    Coil connections (4R) - - 3/4" - 3/4" - - 3/4" - 3/4" - - 3/4" - 3/4" - (3R) 1/2" 1/2" - 1/2" - 3/4" 3/4" - 3/4" - 3/4" 3/4" - 3/4" - 3/4" (1R) 1/2" 1/2" - 1/2" - 1/2" 1/2" - 1/2" - 1/2" 1/2" - 1/2" - 1/2"

    Speed connectedP H V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3 V3P M V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2 V2P L V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1

    Power supply 230V/1/50Hz

    H max. speed; M med. speed; L min. speedHeating mode2 pipes system configuration(1) Room air temperature 20C b.s.; Inlet water temperature 70C; T water 10C2 pipes system configuration (EUROVENT)(2) Room air temperature 20C b.s.; Inlet water temperature 50C; Water flow rate as in cooling mode4 pipes system configuration (with additional heat exchanger) (EUROVENT)(3)Room air temperature 20C b.s.; Inlet water temperature 70C; T water 10CCooling mode (EUROVENT)(4) Room air temperature 27C b.s./19C b.u.; Inlet water temperature 7C; T water 5C(5) Sound power level on the basis of measurements made in compliance with Eurovent 8/2(6) Sound pressure level (A-weighted) measured in the room with volume V=85m3, reverberation time t = 0.5 s; Direction factor Q = 2; Distance r = 2.5mNote: The speed of associates may differ from the standard factory configuration, for more information refer to the program selection and the technical documentation available on the website www.aermec.com

    L7 L6 L5 L4 L3 L2 L1V1 V2 V3 V4 V5 V6 V7

    L6 L5 L4 L3 L2 L1 V1 V2 V3 V4 V5 V6

    Speed

    motor connected

    FCX2250

    FCX6282

    17 22/24 32/34/36 42/44 50/54/56 62/64 82/84 102E 330 440 671 891 891 1102 1102 1102F 41 41 41 41 41 41 41 41G 101 101 101 101 101 107 107 107H 74 74 74 74 74 68 68 68I 49 49 49 49 49 32 32 32L 144 144 144 144 144 253 253 253M 260 260 260 260 260 273 273 273

    Dimensions (mm)

    A

    D

    B

    C

    FCX_P (standard coil/augmented coil)

    * Overall dimensions

    Mod FCX_P 17 22 /24 32/34/36 42/44 50/54/56 62/64 82/84 102Height A 453 453 453 453 453 558 558 558

    WidthB* 452 562 793 1013 1013 1147 1147 1147D 412 522 753 973 973 1122 1122 1122

    Depth C 216 216 216 216 216 216 216 216Weight kg 11 13 18 22 22 33 33 33

    B

    E

    388

    40

    9x20

    E

    350

    98

    9x20B

    F G H

    I

    L

    M

    F G H

    I

    L

    M

    FCX_P 20-30-36-40-50-56 (standard coil)FCX_P 24-34-44-54 (augmented coil)

    FCX_P 80 (standard coil)FCX_P 84 (augmented coil)

  • 34

    Fan coils with Brushless Inverter motor (EC)In-duct installationFCXI P

    Recessed fan coils with inverter technology, for heating, cooling and dehumidifying, specific to work in sensible environment.Equipped with inverter Brushless motor for an high effciency and a continuos air flow rate modulation in order to increased comfort and guarantee electric saving. The inverter motor allows a better air temperature regulation on based on the real indoor envirorement require-ments without temperature swinging. The FCXI P are the ideal solution for 2/4-pipe sys-tems and for tertiary and commercial installations.

    Versions:FCXI P: wall/ceiling mounted without cabinetFCXI PBV: wall/ceiling mounted without cabinet with double circuit coil for 4-pipe system with standard connections (left)FCXI PBVD: wall/ceiling mounted without cabinet with double circuit coil for 4-pipe system with right connectionsThe hydraulic connections of the BV and BVD versions, up to size 56, are not reversible during installation. Specify the connection side when placing the order. Brushless motor with 0-100% speed continuous variation to guarantee best performance at very low sound level Centrifugal fan designed to guarantee continu-

    ous modulation of the air flow rate and to increase comfort and electric saving.

    Unit with standard coil (20 80) Unit with larger coil (24 84) Low pressure drop Air filter with easy extraction and cleaning Removable augers for easy and effective clean-

    ing Reversibility of the hydraulic connections in the

    installation phaseA specific wall-control range is available for the FCXI P. Choose between these panels for simple and complete regulation. Refer to the specific sheet for further details.

    Features

    ELECTRIC SAVING EQUAL TO 50% COMPARED TO A FAN COIL WITH 3-SPEED MOTOR

    FULLY SILENT FUNCTIONING FULL COMFORT: REDUCED TEMPERATURE AND RELATIVE HUMIDITY OSCILLATIONS

    Accessories

    WMT21: Electronic thermostat with LCD display (wall installation).

    SWAI: Water temperature probe for WMT21 elec-tronic thermostat.

    VMF System: Find the features in the specific sheets. AMP: Kit for wall/ceiling mounted installation. BC: Auxiliary condensate drip tray. BV: Hot water coil with one row. It is not available

    for versions with 4 rows or with Plasmacluster. Specify the connection side in case of in-site

    assembly. PMZ: Plenum with motorised dampers (refer to the

    specific sheet for further details). CHF: The VentilCassaforma is a galvanised sheet

    steel template, for P versions, which allows you to obtain a space for housing the fan coil, directly in the wall.

    DSC4: Device for draining condensate. GA: Intake grid with fixed louvers. GAF: Intake grid with fixed louvers with filter.

    GM: Flow grid with adjustable louvers. MA: Protective cabinet, type A (use BC 4 tray

    accessory). MU: Protective cabinet, type U (use BC 5-6 tray

    accessory if horizontal or use BC 4 if vertical). PA: Galvanised sheet steel intake plenum

    equipped with intake fittings for circular section ducts.

    PA-F: Intake plenum, which allows recovery and flow on the same side. It is suitable for all those installations outside air-conditioned rooms, in order to minimise noise and facilitate maintenance operations.

    PM: Galvanised sheet steel flow plenum, external-ly insulated, equipped with plastic flow fittings for ducts and circular sections.

    RD: Straight flow fitting